14 Commissioning Instructions
Before applying power to the panel, any solenoids or igniting actuators must be physically isolated from
the panel by disconnecting both wires, this will prevent any accidental release of extinguishant.
When power is applied and all connections are correct, only the green Power On and either the
Automatic/Manual or Manual Only indicators should be lit.
If any fault indicators are lit, the wiring to the appropriate input or output should be checked an all faults
cleared before proceeding.
Once the panel is fault free, it can be configured with the desired options as described in section 7.
Once the panel has been configured, the system should be thoroughly tested to ensure that the control
panel responds as expected and required.
After satisfactory testing, any final connections should be made (such as to the extinguishing release
actuator).
A record of the configuration options that have been set should be recorded in the tables below and
provided as part of the documentation recommended by BS5839:Part 1:2002 section 40.2 b).
Detection section
CODE FUNCTION
TICK IF SET
00
SOUNDER DELAY TIME = 30 SECONDS
01
SOUNDER DELAY TIME = 1 MINUTE
02
SOUNDER DELAY TIME = 2 MINUTES
03
SOUNDER DELAY TIME = 3 MINUTES
04
SOUNDER DELAY TIME = 4 MINUTES
05
SOUNDER DELAY TIME = 5 MINUTES
06
SOUNDER DELAY TIME = 6 MINUTES
07
SOUNDER DELAY TIME = 7 MINUTES
08
SOUNDER DELAY TIME = 8 MINUTES
09
SOUNDER DELAY TIME = 9 MINUTES
10
COMMON ALARM MODE (default)
11
TWO-STAGE ALARM MODE
12
ZONED ALARM MODE
21*
DISABLE FIRE BUZZER
22*
DISABLE FAULT OUTPUT
23
DISABLE EARTH FAULT MONITORING
24
PULSED REMOTE CONTROL OUTPUT
25
ENABLE SOUNDERS ON DETECTION CIRCUITS
26
DISABLE FIRE OUTPUT
27
DO NOT CHANGE
31
ZONE 1 ALARM FROM DETECTOR DELAYED
32
ZONE 2 ALARM FROM DETECTOR DELAYED
33
ZONE 3 ALARM FROM DETECTOR DELAYED
34
ZONE 4 ALARM FROM DETECTOR DELAYED
35
ZONE 5 ALARM FROM DETECTOR DELAYED
36
ZONE 6 ALARM FROM DETECTOR DELAYED
37
ZONE 7 ALARM FROM DETECTOR DELAYED
38
ZONE 8 ALARM FROM DETECTOR DELAYED
41
ZONE 1 ALARM FROM CALL POINT DELAYED
42
ZONE 2 ALARM FROM CALL POINT DELAYED
43
ZONE 3 ALARM FROM CALL POINT DELAYED