TM204
37 of 56
Issue 1.1
8
Panel Operation – Access Levels 1 and 2
8.1
Normal Condition
Under normal conditions and with all modules in Manual & Auto mode, control panels will have only the
green, Power On LED lit on the detection and extinguishing modules. With the ENABLE CONTROL
keyswitch off, the display on the detection part of the panel will be blank and, the LCDs on the
extinguishing modules will show:
Any modules that are in Manual Only mode will have an additional, Manual only yellow LED lit and their
display will show:
The control panel has 3 Access Levels. Access Level 1 is available at all times and allows operation of
the Alarm/Fault warning Buzzer Silence and Lamp Test buttons on the detection part of the panel only.
Access Level 2 is enabled after operation of the front panel mounted ENABLE CONTROL keyswitch.
Access Level 3 allows configuration options to be set on both the detection part of the panel and the
extinguishing modules following operation of their respective Write Enable switches at Access Level 2
(ENABLE CONTROL keyswitch operated).
When the ENABLE CONTROL keyswitch is operated (Access Level 2) the 7-segment display on the
detection module will show
and the LCDs on the extinguishing modules will show:
8.2
Detection Module – Access Level 2
8.2.1
Test Mode
It is possible to put one or more zones into test mode. When a zone is in test mode it will self reset after
a few seconds. This enables the system to be tested without having to reset the control panel to between
device activations.
To put a zone into test mode, switch the ENABLE CONTROL keyswitch on.
The 7 segment display will show
(test zone 1). To put zone 1 into test mode, press the ENTER
button on the detection module.
The display will now show a flashing dot next to the
and the yellow test LED will be lit.
To select further zones to put into test mode, press the Select button and then the ENTER button so that
the flashing dot appears next to the selected display e.g.
To remove a zone from test mode, press the SELECT button to reveal any zones that have a flashing
dot and then press the ENTER button to take that zone out of test mode. Once all zones have been
taken out of test mode, the yellow, test LED will go off.
8.2.2
Disable Zones
It is possible to disable one or more zones on the FireBeta XT+. When a zone is disabled it will not report
fire or fault conditions. This enables the system to be worked on without false fire or fault conditions
being displayed.
To disable one or more zones, switch the ENABLE CONTROL keyswitch on.