TM204
42 of 56
Issue 1.1
Note:
Pressing the SILENCE/SOUND ALARM button whilst the control panel is in the silenced condition will
cause the sounders to operate again.
The sounders can be toggled on and off with the Silence/Sound alarm button as required.
8.7
Reset
To reset the panel, insert the ENABLE CONTROL key, turn to the right then press the RESET button.
The extinguishing module will reset only after the reset inhibit timer has expired once the activated
condition has been established.
8.8
Detection Zone Fault
Removal of a detector from its base or a fault on any of the zone wiring will cause the General Fault LED
and relevant Zone Fault LED to flash, indicating the zone in which the fault has occurred.
8.9
Sounder Fault
A fault on the wiring to the detection module sounder circuits will cause the General Fault LED to light
and the Sounder Fault LED to flash.
A fault on the sounder circuits of the extinguishing modules will light the Fault LED on the detection
module as well as the extinguishing module. The extinguishing module will display:
Or
8.10 Power Fault
Failure of the mains power or disconnection of the standby battery supply will cause the Fault and Power
Fault LEDs to light on the detection module, indicating an abnormality in the power supply to the control
panel. There will be no indication of this condition on the extinguishing modules.
8.11 System Fault – Detection Module
The system fault and general fault LEDs will light if the configuration memory has not been set or has
become corrupted.
8.12 System fault – Extinguishing module
The System Fault and general fault LEDs will light if the configuration memory has not been set or has
become corrupted.