
TM204
32 of 56
Issue 1.1
To change the time, press the (+) or (-) buttons until the required time is displayed
To save the settings, slide the WRITE ENABLE switch gently to the right.
The extinguishing release time will now be set to the chosen value.
7.2.7
2
nd
Stage Alarm
The second stage alarm output can be configured to be steady or pulsing at about 1 second on, 1
second off to suit the desired application. The factory default for the second stage alarm is pulsing.
To change the operation of the second stage sounders, switch on the ENABLE CONTROL keyswitch
and slide the WRITE ENABLE switch on the module to be configured gently to the left. Press the ENTER
button on the extinguishing module then press the (+) button until the display shows:
Press the ENTER button and the display will show:
To change to steady second stage alarms, press the ENTER button.
To save the settings, slide the WRITE ENABLE switch gently to the right.
The second stage alarm output will operate in steady mode when the module is activated.
7.2.8
Released Indication
It is possible to select whether the released indication on a module is operated at the same time as the
extinguishing release output operates, or by operation of a pressure switch connected to the released,
pressure switch input.
The factory default setting is for the released indication to be operated by operation of a pressure switch
connected to the released pressure switch input.
To change the operation of the released indication, switch on the ENABLE CONTROL keyswitch and
slide the WRITE ENABLE switch on the module to be configured gently to the left. Press the ENTER
button on the extinguishing module then press the (+) button until the display shows:
Press the ENTER button and the display will show:
To change setting, press the ENTER button.
To save the settings, slide the WRITE ENABLE switch gently to the right.
The released indicator will now be lit when the extinguishing output operates.