TM204
11 of 56
Issue 1.1
Although the current consumption of many detection devices would allow more than 32 to be connected
to a zone, this number should be limited to 32 to ensure that a short or open circuit on the wiring does
not prevent the indication of a fire alarm from more than 32 fire detectors and/or call points as required
by European standard EN54-2. If an active end of line LCMU (K14060) is used fit a maximum of 20
detectors per zone.
Table 3 - Compatible detector bases and call points
Model
Type
Manufacturer
Comments
YBN-R/6
STANDARD WITH REMOTE LED
Hochiki
YBO-R/4(IS)
STANDARD WITH REMOTE LED (I.S.)
Hochiki
YBN-R/6SK
DIODE BASE
Hochiki
Must be used with
LCMU
YBO-R/6R
STANDARD LATCHING RELAY
Hochiki
YBO-R/6RN
STANDARD NON-LATCHING RELAY
Hochiki
YBO-R/6RS
DIODE BASE WITH LATCHING RELAY
Hochiki
Must be used with
LCMU
ECO1000R
STANDARD
System Sensor
ECO1000BRSD
DIODE BASE
System Sensor
Must be used with
LCMU
456821-200
STANDARD BASE
Apollo
456821-201
DIODE BASE
Apollo
Must be used with
LCMU
ORB-MB-00001-APO
Timesaver Base
Apollo
ORB-DB-00003-APO
Timesaver Diode Base
Apollo
ORB-RB-10004-APO
Timesaver Relay Base
Apollo
MXT+1
470 OHM CALL POINT
KAC
CX
470 OHM CALL POINT
Fulleon
NXT+-T
CALL POINT
Nittan
ELECTRONICS FREE BASES
ALL
Note: LCMU (Line Continuity Monitoring Device) part number TBA allows call points mounted down line
of detectors that have been removed from diode bases to continue to operate.
Table 4 - Compatible sounders
Model
Type
Manufacturer
Comments
BANSHEE
ELECTRONIC
VIMPEX
WAFER
ELECTRONIC
VIMPEX
FIRECRYER RANGE
ELECTRONIC VOICE
VIMPEX
KOBELL
MOTORISED
VIMPEX
ASKARI
ELECTRONIC
FULLEON
ROSHNI
ELECTRONIC
FULLEON
SQUASHNI
ELECTRONIC
FULLEON
SYMPHONI
ELECTRONIC
FULLEON
ELECTRONIC BELL
ELECTRONIC
FULLEON
CFB BELLS
MOTORISED
FULLEON
B6 AND B8 BELLS
SOLENOID
FULLEON
Table 5 - Compatible I.S. barriers
Model
Type
Manufacturer
MTL5061
DETECTION ZONE GALVANIC ISOLATOR
MTL
MTL778ac
ALL SOUNDER CIRCUITS
MTL
Note: Use galvanic isolator with Hochiki or Apollo detectors only