TM204
27 of 56
Issue 1.1
When the required code number is displayed, pressing the ENTER button will cause the dot on the units
seven segment display to flash. This indicates that a configuration option has been set.
To review which configuration options have been set previously, simply scroll through numbers 1 to 99,
A1 to A8, C1 to C8 and E1 to E8 and those with a flashing dot indicate which options have been set.
Example display showing option set and not set
Table6 – Detection module configuration
CODE
FUNCTION
COMMENTS
00
SOUNDER DELAY TIME = 30 SECONDS
01
SOUNDER DELAY TIME = 1 MINUTE
02
SOUNDER DELAY TIME = 2 MINUTES
03
SOUNDER DELAY TIME = 3 MINUTES
04
SOUNDER DELAY TIME = 4 MINUTES
05
SOUNDER DELAY TIME = 5 MINUTES
06
SOUNDER DELAY TIME = 6 MINUTES
07
SOUNDER DELAY TIME = 7 MINUTES
08
SOUNDER DELAY TIME = 8 MINUTES
09
SOUNDER DELAY TIME = 9 MINUTES
Sets the time delay before sounders operate in combination with
configuration codes 31 to 48 and Access Level 2 function Ad.
10
COMMON ALARM MODE (default)
All sounders operate upon any fire condition
11
TWO-STAGE ALARM MODE
Not used
12
ZONED ALARM MODE
Not used
21*
DISABLE FIRE BUZZER
Buzzer will not operate on fire condition
22*
DISABLE FAULT OUTPUT
Fault relay will not operate except upon total power failure
23
DISABLE EARTH FAULT MONITORING
Connection of fire alarm wiring will not announce a fault
24
PULSED REMOTE CONTROL OUTPUT
Aux 24V supply pulses 1 sec on/1 sec off
25
ENABLE SOUNDERS ON DETECTION CIRCUITS
Not used
26
DISABLE FIRE OUTPUT
Fire relay will not operate upon any alarm
27
DO NOT CHANGE
DO NOT CHANGE
31
ZONE 1 ALARM FROM DETECTOR DELAYED
32
ZONE 2 ALARM FROM DETECTOR DELAYED
33
ZONE 3 ALARM FROM DETECTOR DELAYED
34
ZONE 4 ALARM FROM DETECTOR DELAYED
35
ZONE 5 ALARM FROM DETECTOR DELAYED
36
ZONE 6 ALARM FROM DETECTOR DELAYED
37
ZONE 7 ALARM FROM DETECTOR DELAYED
38
ZONE 8 ALARM FROM DETECTOR DELAYED
Sounder outputs will be delayed by time set at options
0-9 when selected zone(s) triggered by detector only.
Note Access Level 2 function Ad must be set for this to take
effect.
41
ZONE 1 ALARM FROM CALL POINT DELAYED
42
ZONE 2 ALARM FROM CALL POINT DELAYED
43
ZONE 3 ALARM FROM CALL POINT DELAYED
44
ZONE 4 ALARM FROM CALL POINT DELAYED
45
ZONE 5 ALARM FROM CALL POINT DELAYED
46
ZONE 6 ALARM FROM CALL POINT DELAYED
47
ZONE 7 ALARM FROM CALL POINT DELAYED
48
ZONE 8 ALARM FROM CALL POINT DELAYED
Sounder outputs will be delayed by time set at options
0-9 when selected zone(s) triggered by call point only.
Note Access Level 2 function Ad must be set for this to take
effect.
DOT
FLASHING
NO DOT
ZONE 1 I.S. BARRIER
OPTION SET
ZONE 1 I.S. BARRIER
OPTION NOT SET