TM204
49 of 56
Issue 1.1
The tables below can be used to calculate the loading for all models by adding the loads in the second
column.
23911-K087 - 4 zone single area
Current in milliamps
Detection section max alarm load
210
Extinguishing module max alarm load
105
Detection section total sounder load (S1&S2)
Detection section Aux 24V supply
Extinguishing module total sounder load
Extinguishing module Extinguishing output load
Extinguishing module Aux 24V supply
TOTAL LOAD (must be less than 3A)
23911-K085 - 4 zone two area
Current in milliamps
Detection section max alarm load
210
Extinguishing module 1 max alarm load
105
Extinguishing module 2 max alarm load
105
Detection section total sounder load (S1&S2)
Detection section Aux 24V supply
Extinguishing module 1 total sounder load
Extinguishing module 2 total sounder load
Extinguishing module 1 Extinguishing output
load
Extinguishing module 2 Extinguishing output
load
Extinguishing module 1 Aux 24V supply
Extinguishing module 2 Aux 24V supply
TOTAL LOAD (must be less than 3A)
23911-K088 - 8 zone two area
Current in milliamps
Detection section max alarm load
550
Extinguishing module 1 max alarm load
105
Extinguishing module 2 max alarm load
105
Detection section total sounder load (S1&S2)
Detection section Aux 24V supply
Extinguishing module 1 total sounder load
Extinguishing module 2 total sounder load
Extinguishing module 1 Extinguishing output
load
Extinguishing module 2 Extinguishing output
load
Extinguishing module 1 Aux 24V supply
Extinguishing module 2 Aux 24V supply
TOTAL LOAD (must be less than 3A)