P/N 06-237058-001
1-33
February 2012
RELEASE-NOTIFICATION
APPLIANCE CIRCUIT
(R-NAC) CARD
Includes three (3) R-NAC Circuits; no limit on number of R-NAC cards in fully
expanded system (if slots available)
End-of-Line Resistor:
10 K, 5%, 1/2 W
Total Voltage Drop at
End-of-Line:
2 V
Max. Supervisory Current:
5mA
Release Output Specifications:
Solenoid-Based Devices:
Actuator-Based Devices:
When solenoid-based releasing devices are used, the output can be wired as
CLASS-A or CLASS-B. When wired as CLASS-A, the circuit is supervised for
opens and short circuits and is power-limited. For CLASS-B wiring, if an In-Line
Releasing Device is included, the circuit is supervised for opens and short
circuits and is power-limited. For CLASS-B wiring, if an In-Line Releasing
Device is NOT included, the circuit is supervised for opens only and is non-
power-limited. Circuits are always supervised for ground faults.
When actuator-based releasing devices are used, only CLASS-B wiring is allowed.
The circuit is supervised for opens and short circuits and is power-limited when
the In-line Releasing Device is used. Circuits are always supervised for ground
faults.
Maximum Devices per
Circuit:
Solenoid-Based Devices: Actuator-Based Devices:
1 Refer to Table C-3 in Appendix C.
Maximum Output Circuit
Terminal Voltage:
28 Vdc 28 Vdc
Minmum Output Circuit
Terminal Voltage:
20 Vdc 20 Vdc
NAC Output Specifications:
Wiring Types / Electrical
Supervision:
–
24 Vdc regulated
–
When NAC devices are used, the output can be wired as CLASS-A or CLASS-B.
–
When configured as a NAC, circuit is supervised and power-limited.
–
When configured as a NAC, either synchronized or non-synchronized strobes
are supported.
Maximum Output Current:
Non-Synchronized: Synchronized:
2.0 A 1.5 A
Maximum Output Circuit
28 Vdc 28 Vdc
Minmum Output Circuit
Terminal Voltage:
20 Vdc 20 Vdc
POWER MANAGEMENT
UNIT (PMU) BOARD
Each Power Management Unit can interface with two AC-to-DC switching power
supplies for a total of 10.8 A @ 27.6 Vdc. Maximum of 4 PMU’s in fully
expanded system.
AC-to-DC Power
Conversion:
1 or 2 switching power supplies per PMU
Primary AC Power Input:
NOTE
: Primary power is
selected by setting the slide
switch on the side of the
power supply.
1 Power Supply Unit: 2 Power Supply Units:
120 Vac, 50/60 Hz, 3.2 A 120 Vac, 50/60 Hz, 6.4 A
240 Vac, 50/60 Hz, 1.6 A 240 Vac, 50/60 Hz, 3.2 A
DC Power Output:
5.4A @ 27.6 Vdc 10.8A @ 27.6 Vdc
Item
Description
Содержание ARIES NETLink
Страница 2: ......
Страница 14: ...Table of Contents February 2012 xii P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 20: ...List of Tables February 2012 xviii P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 78: ...Installation February 2012 2 22 P N 06 237058 001 Figure 2 17 Installing the Expansion Card Cage ...
Страница 112: ...Installation February 2012 2 56 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 166: ...Configuration and Programming February 2012 3 54 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 194: ...Operation February 2012 4 28 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 203: ...Networking P N 06 237058 001 5 9 February 2012 Figure 5 5 Processing Group 0 Networked Control Unit Interactions ...
Страница 222: ...Testing and Maintenance February 2012 6 4 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 250: ...Troubleshooting February 2012 7 28 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 268: ...List of Agency Listed Compatible Devices February 2012 C 4 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 270: ...FM Rules for Preaction Deluge Systems February 2012 D 2 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 286: ...ARIES NETLINK For City Of Chicago Applications February 2012 G 6 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 293: ......