FM Rules for Preaction/Deluge Systems
P/N 06-237058-001
D-1
February 2012
APPENDIX D
FM RULES FOR PREACTION/DELUGE SYSTEMS
ARIES NET
Link
applications which require Factory Mutual (FM) approved Pre-Action and/or Deluge
Systems must conform to the following guidelines:
•
Detection Zone 1 (Det1), Detection Zone 2 (Det2) and Waterflow (W'Flow) Initiating Circuits must
be configured for CLASS-A, Style D wiring.
•
The Battery backup system must provide for 90 hours of Standby operation followed by 10
minutes of Alarm operation. Refer to Appendix A for calculations.
•
The Agent Release Output must be configured for Deluge Solenoid activation. The Solenoid
Activation Time must be set either for:
–
10 minutes, or
–
15 minutes, or
–
On-until-reset.
The wiring connection of the control unit to the Deluge Solenoids must be as detailed in the
Installation section of this manual.
Содержание ARIES NETLink
Страница 2: ......
Страница 14: ...Table of Contents February 2012 xii P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 20: ...List of Tables February 2012 xviii P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 78: ...Installation February 2012 2 22 P N 06 237058 001 Figure 2 17 Installing the Expansion Card Cage ...
Страница 112: ...Installation February 2012 2 56 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 166: ...Configuration and Programming February 2012 3 54 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 194: ...Operation February 2012 4 28 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 203: ...Networking P N 06 237058 001 5 9 February 2012 Figure 5 5 Processing Group 0 Networked Control Unit Interactions ...
Страница 222: ...Testing and Maintenance February 2012 6 4 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 250: ...Troubleshooting February 2012 7 28 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 268: ...List of Agency Listed Compatible Devices February 2012 C 4 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 270: ...FM Rules for Preaction Deluge Systems February 2012 D 2 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 286: ...ARIES NETLINK For City Of Chicago Applications February 2012 G 6 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 293: ......