Troubleshooting
February 2012
7-26
P/N 06-237058-001
ATMAddr Not Registered On
The control unit has not been set up to
expect the ATM at ATM RS-485 circuit
address Addr.
• Register the ATM if part of system
configuration. See Paragraph . This
procedure is insufficient. The
following procedure must also be
conducted.
• Upload a new application program
that includes the previously
unregistered ATM.
• De-register the ATM if not part of
system configuration. See Paragraph
3-2.5.2.4.55.
• Check the 24 Vdc power (Terminal
Block TB3)and RS-485
communications wiring (Terminal
Blocks TB1 and TB2) from the
control unit to the ATM
• Ensure that the ATM Address Switch
S1 is set correctly.
• Refer to ATM Installation Manual, P/N
06-236179-002.
ATMAddr PSU Fault On
A loss of 24 Vdc power at Terminal
Block TB3 or an open circuit in the
monitoring circuit from the ATM's "PS
Flt" and "Com" terminals to the
normally-closed trouble contacts of its
associated remote power supply
• Refer to ATM Installation Manual, P/N
06-236179-002.
• Check for 24 Vdc power at ATM
Terminal Block TB3.
• Look for discontinuity in wiring to
remote-power-supply trouble
contacts. Jumper these terminals if
you are using the ARIES NET
Link
Control Unit to power the ATM.
• Check for trouble with third-party
remote power supply.
ATMAddr Reset Input Fault On
An open circuit in wiring from the
ATML's "Reset" input terminal to the
associated annunciator's reset switch.
ATM-L address is Addr.
• Refer to ATM Installation Manual, P/N
06-236179-002.
• Look for discontinuity in wiring to
reset switch
• Check for missing 10k end-of-line
resistor.
ATMAddr Silence Input Fault On
An open circuit in wiring from the
ATML's "Silence" input terminal to the
associated annunciator's alarm-silence
switch. ATM-L address is Addr.
• Refer to ATM Installation Manual, P/N
06-236179-002.
• Look for discontinuity in wiring to
alarm-silence switch
• Check for missing 10k end-of-line
resistor.
ATMAddr Silenced Output Fault
On
An open circuit in wiring from the
ATML's "Silence" output terminal to the
associated annunciator's alarm-silence
LED. ATM-L address is Addr.
• Refer to ATM Installation Manual, P/N
06-236179-002.
• Look for discontinuity in wiring to
alarm-silence LED (if used)
• Check for missing 20k supervising
resistor if alarm-silence LED not
used
Table 7-7. ATM Events
ATM Events
Error Message
Probable Cause
Corrective Action
Содержание ARIES NETLink
Страница 2: ......
Страница 14: ...Table of Contents February 2012 xii P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 20: ...List of Tables February 2012 xviii P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 78: ...Installation February 2012 2 22 P N 06 237058 001 Figure 2 17 Installing the Expansion Card Cage ...
Страница 112: ...Installation February 2012 2 56 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 166: ...Configuration and Programming February 2012 3 54 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 194: ...Operation February 2012 4 28 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 203: ...Networking P N 06 237058 001 5 9 February 2012 Figure 5 5 Processing Group 0 Networked Control Unit Interactions ...
Страница 222: ...Testing and Maintenance February 2012 6 4 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 250: ...Troubleshooting February 2012 7 28 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 268: ...List of Agency Listed Compatible Devices February 2012 C 4 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 270: ...FM Rules for Preaction Deluge Systems February 2012 D 2 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 286: ...ARIES NETLINK For City Of Chicago Applications February 2012 G 6 P N 06 237058 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 293: ......