OPERATION MANUAL

RK-2006SPGM

Pellet fuel burner fitted boiler temperature controller.

Version 5701

+MZS

Содержание RK-2006SPGM+MZS

Страница 1: ...OPERATION MANUAL RK 2006SPGM Pellet fuel burner fitted boiler temperature controller Version 5701 MZS...

Страница 2: ...Information on burner work 15 Alarms cancellation 15 Setting the parameters service mode 15 Table 3 Table service parameter 16 Language selection 18 Brightness saturation contrast of the display 18 S...

Страница 3: ...locations that shall be dry Figure 2 presents the electrical con nection diagram For connection of stoker alarm indicator and ash removal system the additional module UM 1 shall be applied CAUTION Bef...

Страница 4: ...of the device is to set the preset boiler temperature In this hands U need to turn the boiler thermostat knob 4 to set the correct value and confirm it with the OK button or press the knob CAUTION If...

Страница 5: ...p work indicator 9 Burner capacity indicator the higher the capacity the brighter the flame 10 Cleaning device work indicator 11 Stoker work indicator 12 Feeder temperature 13 The operation indicator...

Страница 6: ...water pumps operation but automatic ignition does not follow AUGER EXTINCT EMERGENCY SHUT DOWN Fuel ignition in auger channel The controller empties ignited fuel from the auger channel until temperatu...

Страница 7: ...feeding rate is adjusted by the technician Pressing STOP button exceeding time limit for cleaning thermostat contacts opening or if water temperature in domestic water tank is obtained during operati...

Страница 8: ...uence Afterburning EXTINCTION CLEANING Automatic burner cleaning occurs after time set limit by programmer In this mode controller starts cleaning system for preset time After this procedure controlle...

Страница 9: ...y the technician Out of fuel alarm will be activated To turn on the controller again first refill fuel cancel the alarm with STOP button and begin setting up process by pressing START button Emergency...

Страница 10: ...activates the pump absolutely CO The increase in water temperature in the boiler to the value programmed in parameter service TEMPERATURE BOILER OVERHEAT will turn off the fan heating pump switch the...

Страница 11: ...the para meter will be backlit You can change the value of the selected parameter by turning the knob To confirm the change press the knob again and the controller will return to the list of paramete...

Страница 12: ...he WOOD fuel is set you can burn the wood in the pellet boiler the controller operates at the wood fuel burning settings WOOD PELLET once the wood has been burned the controller switches to pellet bur...

Страница 13: ...ivation of program for bacterial flora liquidation in domestic water tank When YES is selected it activates the process of heating the domestic water tank above 75 C When the required temperature is o...

Страница 14: ...the system is fitted with flame temperature detector parameters change and viewing is unavailab le 1 13 The current furnace brightness determined by an optical detector this parameter displays the cu...

Страница 15: ...ncellation The parameter enables the user to cancel the alarms recorded in the controller data storage 1 20 Burner mode INTERMITTENT turning off the thermostat will cause the controller to switch into...

Страница 16: ...of parameters is possible by turning the multifunction knob possible to edit the parameter is highlighted After selecting the desired parameter press the OK button knob and enter the subgroups of a gi...

Страница 17: ...r power 1 100 F 4 6 Fuel feed for min burner power 1 100 F 4 7 Stoker work mode see description 4 8 Stoker work time 1s 99s 4 9 Stoker pause time 1s 99s 4 10 Stoker extra work time 1s 99s 4 11 Stoker...

Страница 18: ...r modulation factor 1 20 F 9 9 The operating mode of the thermostat NORMAL ADAPTIVE WEATHER F 9 10 The time constant adaptation 1min 99min F 9 11 Burner switch off delay 0min 99min F 9 12 Lowering the...

Страница 19: ...roller it is possible to test various output devices This feature is available in service mode only if the adju stment process is stopped ie The regulator before entering the service mode was in STOP...

Страница 20: ...peed during boiler start setting After time expire the controller will increase fan speed up to the selected Max fan speed during boiler start setting 3 5 Fan speed during ignition this parameter desc...

Страница 21: ...accumulated gases 3 11 Fan scavenge air purging blow time this parameter specifies blow time 3 12 Fan scavenge air purging pause time this parameter specifies pause time during scavenge This setting i...

Страница 22: ...hat is fed to the burner during lighter operation The programmed setting specifies feeding time in percent in relation to the time of whole work cycle Selection of 0s setting will switch fuel feeding...

Страница 23: ...ed with Stoker extra work time setting 4 8 Stoker work time this parameter specifies operation time of the stoker in who le work cycle This setting is unavailable if the stoker is switched off or in a...

Страница 24: ...emergency input is not used NO parameter shall be selected in Auger ignition test setting and contacts of X input shall be closed 4 13 Auger ignition temperature this parameter specifies auger tempera...

Страница 25: ...tion procedure is started when the temperature drops or the brightness of the flame to the value of 0 5 5 Flame failure detection delay this parameter specifies how long after the launch procedures fo...

Страница 26: ...arameter determines the maximum operating time of stabilization firing This parameter is not available if the parameter STABILIZATION OF FIRING is set to NO 5 12 Smooth stabilization of ignition setti...

Страница 27: ...eaning means burner shut down and start cleaning mechanism for the time set in parameter Cleaning mechanism work time After turning off the regulator output deducts the time set in parameter Cleaning...

Страница 28: ...ode It specifies the time required for the mechanism retraction to the rest position after turning off the control output 6 4 Cleaning mechanism pause time this parameter is available only when the cl...

Страница 29: ...AUTO or COMBI mode Specifies how many hours the burner can work without cleaning If the maximum time is reached the cleaning will run even if there was no required number of shut downs 7 x Central hea...

Страница 30: ...ing will switch domestic water in the circuit purposed for control of the mixing pump In this case return water temperature sensor shall be connected instead of domestic water sensor and the mixing pu...

Страница 31: ...ation In this case after wor king for the hot water boiler water temperature may be higher than the temperature required to heat the rooms This may result in extinction of the burner due to excee ding...

Страница 32: ...r works in burner minimum power mode and boiler temperature increase follows by this programmed setting the controller will start burner extinction shut down 9 4 Burner power switching hysteresis when...

Страница 33: ...mostat with contact output Contacts of the thermostat is signaled by the appearance of the ther mometer symbol in the index of the thermostat CAUTION The entrance of the room thermostat is active only...

Страница 34: ...g external conditions we observe frequent overhea ting of the rooms increase the time constant During niedogrzewania value should be reduced 9 11 Burner off delay this parameter determines the time of...

Страница 35: ...attributed to your controller and to avoid errors when a number of devices are switched to the bus Default value 1 10 3 MODBUS channel capacity selection of the RS 485 transmission speed Default valu...

Страница 36: ...ERVICE changing all of the parameters is possible 10 6 Terminal access level defines to what extent access can be obtained through the remote terminal NO no access through the remote terminal READ OUT...

Страница 37: ...ycle in depending on the characteristics of the weather and room tempera ture AUTO the pump runs continuously The mixing valve keeps the temperature of the second circuit only depending on the charact...

Страница 38: ...s the minimum boiler temperature that will be set on the boiler 13 7 The hysteresis circuit 2 parameter determines how much the temperature must fall the second circuit to control heat attached 13 8 T...

Страница 39: ...h an external temperature sensor this parameter allows you to specify whether the sensor is installed In the absence of this parameter the sensor has to be turned off 14 2 Point 0 heating curve temper...

Страница 40: ...he controller 8 Technical Data Power Supply 230 V 10 50 Hz Power consumption without fan and pump 2 VA Temperature measurement range KTY 81 210 39 109 C 1 C Temperature measurement range PT 1000 30 50...