3
Technical data
3.1
Pump GTF / system
Information / pump type
GTF 500
GTF 500 resistant
Mono / Duo
GTF 1200
Mono / Duo
Weight of Pump / system
19.9 kg / 22.8 kg
24.9 kg / 35.7 kg
Power P1 / P2
600 W / 360 W
1400 W / 840 W
Speed
2800 rpm
2650 rpm
Operating voltage
230 V; 50 Hz
230 V; 50 Hz
Nominal current (per pump)
2.7 A
6.2 A
Max. pumping capacity
10 m³/h
15 m³/h
Max. pumping height
8 m
9 m
Completely free passage
10 mm
30 mm
Max. temperature
Pumped medium
35 °C
Protective rating
IP68 (3m WC)
Protection class
I
Motor protection
integrated
Connection type
Schuko earthed safety plug / control unit
Recommended fuse
C16A
Operating mode
S1
Load class
K3/L15
Inlet
DN100
Groundwater resistance
3 m
3.2
Dimensions
EN
016-059