BHK-MG (OPR) 032816
3-51
FIGURE 3-19. SLOW MODE/FAST MODE OPERATION
If desired, an external output capacitor can also to be used; the following instructions apply
when using an external output capacitor:
a. Use a capacitor rated to more than the maximum output voltage of the power supply. If
a series combination of polarized type capacitors is used, potential equalizer resistors
in parallel with each capacitor should be installed and attention should be paid to the
polarity of the capacitors: the “plus” terminal of each capacitor is connected to the
“minus” terminal of the next capacitor, if present, or to +OUT terminal of the power sup-
ply (see Figure 3-19).
b. If precise control of the voltage across the external capacitor is desired, use remote
sensing: connect the sensing leads and power leads across the external output capaci-
tor and connect the load to the external capacitor.
c. If the external capacitor has a value much smaller than internal output capacitor C
OUT
(see Table 1-2), then it is not necessary to connect the internal capacitor at the output
using the link between terminals TB1-6 and TB1-7. If the external capacitor is compara-
Содержание BHK 1000-0.2MG
Страница 2: ......
Страница 6: ......
Страница 17: ...BHK MG032816 xi FIGURE 1 1 BHK MG SERIES PROGRAMMABLE POWER SUPPLY ...
Страница 18: ...xii BHK MG032816 ...
Страница 24: ...1 6 BHK MG OPR 032816 FIGURE 1 2 BHK SERIES POWER SUPPLY MECHANICAL OUTLINE DRAWING SHEET 1 OF 2 ...
Страница 25: ...BHK MG OPR 032816 1 7 FIGURE 1 2 BHK SERIES POWER SUPPLY MECHANICAL OUTLINE DRAWING SHEET 2 OF 2 ...
Страница 46: ......
Страница 101: ...BHK MG OPR 032816 3 55 FIGURE 3 20 SERIES AUTOMATIC CONFIGURATION ...
Страница 109: ...BHK MG OPR 032816 3 63 FIGURE 3 23 PARALLEL AUTOMATIC CONFIGURATION ...
Страница 114: ...3 68 BHK MG OPR 032816 FIGURE 3 25 PARALLEL MASTER SLAVE CURRENT MODE CONFIGURATION ...
Страница 116: ......
Страница 154: ......