1-4
BHK-MG (OPR) 032816
OUTPUT CHARACTERISTICS (CONTINUED)
Withstand voltage
(All models) 1350V a-c/1 min
Between shorted inputs and chassis
BHK 300-0.6MG 1950V d-c/1 min
Between shorted outputs and chassis.
BHK 500-0.4MG 2250V d-c/1 min
BHK 1000-0.2MG
2800V d-c/1 min
BHK 2000-0.1MG
Chassis connection to ground
resistance
100 mohms max.
Between ground input connection and
chassis @ 30A
Leakage Current
25
A rms /100 uA p-p, for 115V a-c input voltage
(chassis to EARTH-GND)
Enable/Disable Output Power
Local Front panel Keypad
Enables/disables digital programming sig-
nals only. Shutdown line is for disable only
- removing the signal does not reenable
the output (See PAR. 3.2.7.3).
Remote - IEEE 488 (GPIB) port
- RS 232 port
- Trigger port (shutdown
line)
Output Display
Output voltage is displayed with two decimals for BHK 300-0.6MG and
BHK 500-0.4MG and one decimal for BHK 1000-0.2MG and BHK
2000-0.1MG.Output current for all models is displayed with two deci-
mals when current range is set to High, and three decimals when cur-
rent range is set to Low.
Protection
Overtemperature:
See PAR. 1.4.10a
Overvoltage/Overcurrent: 0 to 1.1 x EOmax
0 to 1.1 x IOmax (except
BHK 300-0.6MG)
0 to 1.08 x IOmax (BHK
300-0.6MG only)
See PAR. 1.4.4
Uneven voltage/current
in pass element:
See PAR. 1.4.10c
Fan failure:
See PAR. 1.4.10d
AC line failure:
See PAR. 1.4.10e
Interruption between sens-
ing and power terminals:
See PAR. 1.4.10f
Overload of main or
auxiliary power transformer:
See PAR. 1.4.10g
Internal Output Capacitor
(Default state = internal output
capacitor connected.)
BHK 300-0.6MG 20
F ±6%
All internal output capacitors are
non-polarized type.
BHK 500-0.4MG 10
F ±6%
BHK 1000-0.2MG 4
F±10%
BHK 2000-0.1MG 2
F±10%
Reference Voltages for analog
programming:
+10 ±-0.2V d-c
–10 ±-0.2V d-c
max.10 mA d-c
Status port
Type Output transistor (open collector) from an optocoupler
Output Ratings Ic = 8mA d-c, Vceo = 40V d-c, Pd = 150mW@25 ° C
Logic Saturated transistor when AC line is present
Series Connection
Automatic or Master-
Slave Operation, limited
by the d-c isolation limit
voltage
For slave unit, use analog programming
only.
Parallel Connection
Automatic or Master-
Slave Operation
For slave unit, use analog programming
only.
TABLE 1-2. BHK-MG 200W SPECIFICATIONS (Continued)
SPECIFICATION
RATING/DESCRIPTION
CONDITION
Содержание BHK 1000-0.2MG
Страница 2: ......
Страница 6: ......
Страница 17: ...BHK MG032816 xi FIGURE 1 1 BHK MG SERIES PROGRAMMABLE POWER SUPPLY ...
Страница 18: ...xii BHK MG032816 ...
Страница 24: ...1 6 BHK MG OPR 032816 FIGURE 1 2 BHK SERIES POWER SUPPLY MECHANICAL OUTLINE DRAWING SHEET 1 OF 2 ...
Страница 25: ...BHK MG OPR 032816 1 7 FIGURE 1 2 BHK SERIES POWER SUPPLY MECHANICAL OUTLINE DRAWING SHEET 2 OF 2 ...
Страница 46: ......
Страница 101: ...BHK MG OPR 032816 3 55 FIGURE 3 20 SERIES AUTOMATIC CONFIGURATION ...
Страница 109: ...BHK MG OPR 032816 3 63 FIGURE 3 23 PARALLEL AUTOMATIC CONFIGURATION ...
Страница 114: ...3 68 BHK MG OPR 032816 FIGURE 3 25 PARALLEL MASTER SLAVE CURRENT MODE CONFIGURATION ...
Страница 116: ......
Страница 154: ......