BHK-MG (OPR) 032816
1-11
1.4.10
BUILT-IN PROTECTION
BHK-MG Series Power Supplies provide built-in protection against the following:
a.
Overtemperature of the pass elemen
t. Heatsink temperature is monitored. If an overtem-
perature condition is maintained for more than 0.5ms, the following actions are initiated: the
pass element is cut off and latched off, the output capacitor is discharged, the LCD displays
the error message “BHK FAILURE“ and an error message is sent on the IEEE 488 Bus.
b.
Overvoltage/overcurrent at the output.
See PAR. 1.4.4
c.
Uneven voltage/current in the pass element.
Voltage is monitored across different transis-
tors of the pass element while current is monitored through the different branches. If uneven
voltage/current continues for more than 11ms, the pass element is latched off, the output
capacitor is discharged, the POWER circuit breaker is tripped to OFF and a flag is sent to the
host computer on a dedicated line (Status Port connector)
d.
Fan failure.
If fan current drops below predetermined value continuously for more than
16ms, the pass element is latched off, the output capacitor is discharged, the LCD displays
the error message “BHK FAILURE” and an error message is sent on IEEE 488 Bus.
e.
AC line failure.
If AC line is missing for more than 8 ms, a flag is sent to the host computer
on a dedicated line (Status Port connector). In addition, if the jumper at A7-J12 is installed
(default state), the pass element is latched off, the output capacitor is discharged, and the
POWER circuit breaker is tripped to OFF.
f.
Interruption between the sensing and corresponding power output terminals.
If there
is an interruption between the sensing and power terminals, two diodes connected in parallel
between the sensing lead and the corresponding power lead (one forward biased and one
reverse biased), allow the power supply to continue to function.
g.
Overload of the main or auxiliary power transformer.
If input current of the main trans-
former exceeds 7A a-c @ 115V a-c or 3.5A a-c @ 230V a-c, the input POWER circuit
breaker is tripped to OFF, the pass element is latched off, the output capacitor is discharged,
and a flag is sent to the Status Port connector. The reaction time is inversely proportional to
the input overcurrent: from a minimum of 10ms for 10 times nominal overcurrent, to a maxi-
mum of 100 seconds for 25% above nominal current.
If input current of the auxiliary power transformer exceeds a predetermined value, in most
cases the input POWER circuit breaker is tripped to OFF (if jumper A7J12 is installed), the
pass element is latched off, the output capacitor is discharged, and a flag is sent to the Sta-
tus Port connector. If the cause of the overload is a problem in the protection circuit, the input
POWER circuit breaker may not trip off: the pass element will be latched off and the output
capacitor will discharge more slowly, and a flag is sent to the status port. The reaction time in
this case is determined by PTC (positive temperature coefficient) thermistor A5R1 between
30 and 100 seconds.
h.
Current Limit.
The current through the main branch of the pass element is monitored. If this
current is maintained between 1.8 to 2.2 times larger than the nominal value for more than
11ms, the pass element is latched off, the output capacitor is discharged, and the POWER
circuit breaker is tripped to OFF.
Содержание BHK 1000-0.2MG
Страница 2: ......
Страница 6: ......
Страница 17: ...BHK MG032816 xi FIGURE 1 1 BHK MG SERIES PROGRAMMABLE POWER SUPPLY ...
Страница 18: ...xii BHK MG032816 ...
Страница 24: ...1 6 BHK MG OPR 032816 FIGURE 1 2 BHK SERIES POWER SUPPLY MECHANICAL OUTLINE DRAWING SHEET 1 OF 2 ...
Страница 25: ...BHK MG OPR 032816 1 7 FIGURE 1 2 BHK SERIES POWER SUPPLY MECHANICAL OUTLINE DRAWING SHEET 2 OF 2 ...
Страница 46: ......
Страница 101: ...BHK MG OPR 032816 3 55 FIGURE 3 20 SERIES AUTOMATIC CONFIGURATION ...
Страница 109: ...BHK MG OPR 032816 3 63 FIGURE 3 23 PARALLEL AUTOMATIC CONFIGURATION ...
Страница 114: ...3 68 BHK MG OPR 032816 FIGURE 3 25 PARALLEL MASTER SLAVE CURRENT MODE CONFIGURATION ...
Страница 116: ......
Страница 154: ......