Remote RMM-1400 Version 2.0x Configuration Guide
Remote RMM-1400 Product Overview: RMB Peripheral Units
1-5
RMB Peripheral Units
RMB-1 Peripheral Unit
The RMB-1 peripheral unit (shown in
Figure 1-3
) can be connected to and powered
from one of Remote RMM-1400’s PoE-capable Ethernet ports. RMB-1 adds the
following connectors and counts:
64 digital bistate inputs
Four relay outputs
Four current inputs (4-20 mA)
Four voltage inputs (0-10V, positive only)
A four-terminal SiteBus
Four sets of auxiliary terminals, which are not electrically connected to other
RMB-1 I/O terminals
Built-in temperature and humidity sensors
For details on physically connecting to RMB-1 terminals, see the
Remote RMM-1400
Installation Guide
.
Figure 1-3 RMB-1 Peripheral Unit
RMB-2 Peripheral Unit
The RMB-2 peripheral unit (shown in
Figure 1-4
) offers similar capabilities to RMB-1
in a chassis that is sized to be easily mounted in a standard 19-inch, 21-inch, or 23-
inch rack. RMB-2’s digital bistate inputs support both wet and dry contacts, while
RMB-1’s digital bistate inputs support dry contacts only.
Содержание RMM-1400
Страница 14: ...TOC 6 Table of Contents ...
Страница 30: ...Remote RMM 1400 Version 2 0x Configuration Guide Getting Started Accessing the Web Interface 2 10 ...
Страница 54: ...Remote RMM 1400 Version 2 0x Configuration Guide Configuring Network Setup Parameters Configuring SNMP 5 12 ...
Страница 196: ...Remote RMM 1400 Version 2 0x Configuration Guide Configuring Jobs Configuring Dynamic Memory for a Job 18 14 ...
Страница 206: ...Remote RMM 1400 Version 2 0x Configuration Guide Using Configuration Wizards Using the serial port Wizard 19 10 ...
Страница 242: ...Glossary 30 Glossary ...
Страница 246: ...Copyrights 2 Copyrights and License Statements ...