Remote RMM-1400 Version 2.0x Configuration Guide
Configuring Measurements and the Measurement Table: Configuring an Event Correlation for a
Measurement
13-10
To configure the alarm table entry for the fire danger correlation:
1. At the main prompt, configure the alarm entry name
dooropen
:
config alarm-entry fireDanger
2. Configure the alarm entry
dooropen
with the following parameters:
event originator
correlation
FireDanger
event type
true
event severity
critical
alarm message
Fire alarm exists
config alarm-entry fireDanger event correlation FireDanger true
critical Fire alarm exists
3. Configure the alarm entry
doorclosed
with the following parameters:
event originator
correlation
FireDanger
event type
false
event severity
normal
alarm message
Fire alarm is cleared
config alarm-entry dooropen event correlation FireDanger false
normal Fire alarm is cleared
4. Save the configuration.