Table 3 - Compatible detector bases and call points
Model Type
Manufacturer
Comments
YBN-R/6
STANDARD WITH REMOTE LED
Hochiki
YBO-R/4(IS)
STANDARD WITH REMOTE LED (I.S.)
Hochiki
YBN-R/6SK DIODE
BASE
Hochiki
Must be used with
LCMU
YBO-R/6R STANDARD
LATCHING
RELAY
Hochiki
YBO-R/6RN
STANDARD NON-LATCHING RELAY
Hochiki
YBO-R/6RS
DIODE BASE WITH LATCHING RELAY
Hochiki
Must be used with
LCMU
ECO1000R STANDARD
System
Sensor
ECO1000BRSD
DIODE BASE
System Sensor
Must be used with
LCMU
456821-200 STANDARD
BASE
Apollo
456821-201 DIODE
BASE
Apollo
Must be used with
LCMU
ORB-MB-00001-APO Timesaver
Base
Apollo
ORB-DB-00003-APO
Timesaver Diode Base
Apollo
ORB-RB-10004-APO
Timesaver Relay Base
Apollo
MCP1
470 OHM CALL POINT
KAC
CX
470 OHM CALL POINT
Fulleon
NCP-T CALL
POINT
Nittan
ELECTRONICS
FREE
BASES
ALL
Note: LCMU (Line Continuity Monitoring Device) part number K14060 allows call points mounted down line of
detectors that have been removed from diode bases to continue to operate.
Table 4 - Compatible sounders
Model Type
Manufacturer
Comments
BANSHEE ELECTRONIC VIMPEX
WAFER ELECTRONIC
VIMPEX
FIRECRYER RANGE
ELECTRONIC VOICE
VIMPEX
KOBELL MOTORISED
VIMPEX
ASKARI ELECTRONIC
FULLEON
ROSHNI ELECTRONIC
FULLEON
SQUASHNI ELECTRONIC FULLEON
SYMPHONI ELECTRONIC FULLEON
ELECTRONIC BELL
ELECTRONIC
FULLEON
CFB BELLS
MOTORISED
FULLEON
B6 AND B8 BELLS
SOLENOID
FULLEON
Table 5 - Compatible I.S. barriers
Model Type
Manufacturer
MTL5061
DETECTION ZONE GALVANIC ISOLATOR
MTL
MTL7778ac
ALL SOUNDER CIRCUITS
MTL
Note: Use galvanic isolator with Hochiki or Apollo detectors only
Содержание Sigma XT Plus
Страница 1: ...Sigma XT Extinguishant Control Panel Operation and Maintenance Manual Man 1112 Issue 23 March 2016...
Страница 15: ...Man 1112 Sigma XT _23 Page 15 of 52 Detection panel terminals...
Страница 16: ...Man 1112 Sigma XT _23 Page 16 of 52 Extinguishing module terminals...
Страница 51: ...Man 1112 Sigma XT _23 Page 51 of 52...
Страница 52: ...Man 1112 Sigma XT _23 Page 52 of 52 Man 1112...