Page 30 of 52
15.2.3 Configuring the activation mode
It is possible to configure the extinguishing modules to be activated by coincidence (any 2 zones in a range of
zones) or a single zone in a range of zones. The activation mode is factory set to coincidence.
To change this, switch on the enable controls keyswitch and slide the write enable switch on the module to be
configured gently to the left. Press the ENTER button on the extinguishing module then press the UP button. The
display will show:
ACTIVATION MODE.
= COINCIDENCE
Press the ENTER button and the display will show:
ACTIVATION MODE.
= single ?
Press the ENTER button to select single zone activation mode.
To save the settings, slide the write enable switch gently to the right.
Operation of any of the zones in the range of zones selected to trigger the module (see below) will now put the
module into the activated condition. Coincidence mode must not be set if single activation is required.
15.2.4 Configuring Stage 1 /Hold Output
The ‘1
st
Stage’ relay output is factory set to activate when as a stage 1 alarm contact, it can be re-configured to
activate when the ‘Hold’ input is activated.
To change this, switch on the enable controls keyswitch and slide the write enable switch on the module to be
configured gently to the left. Press the ENTER button on the extinguishing module then press the UP button. The
display will show:
User O/p Mode
= Stage 1
Press the ENTER button and the display will show:
User O/p Mode
= Hold
?
Press the ENTER button to change mode.
To save the settings, slide the write enable switch gently to the right.
15.2.5 Configuring the activation zones
The extinguishing modules are factory set to be activated by coincidence activation of the logical zones in the
detection part of the panel and are addressed logically from 1 to 4.
This means that on an 8 zone, 4 extinguishing area panel for instance, zones 1 and 2 will be set to activate the
extinguishing module at address 1, zones 3 and 4 will be set to activate the extinguishing module at address 2 and
so on.
This can be changed if required so that any zones can activate the extinguishing module.
Note: The number of the first activation zone must be lower than the last activation zone.
To do this, switch on the enable controls keyswitch and slide the write enable switch on the module to be
configured gently to the left. Press the ENTER button on the extinguishing module and then the up button until the
display will shows:
FIRST ACTIV.
ZONE = X
X will be the number of the zone currently selected to be the first activation zone.
This can be changed if required by using the UP and DOWN buttons to select the require zone number. When the
required zone number is displayed, pres the ENTER button. The display will show:
FIRST ACTIV.
ZONE = X ?
X will be the number of the zone selected to be the first activation zone.
Press the ENTER button and then the UP button. The display will then show:
LAST ACTIV.
ZONE = X
X will be the number of the zone currently selected to be the last activation zone.
This can be changed if required by using the UP and DOWN buttons to select the require zone number. When the
required zone number is displayed, pres the ENTER button. The display will show:
last ACTIV.
ZONE = X ?
X will be the number of the zone selected to be the last activation zone.
Activation of any of the zones in the range selected will now contribute to activation of this module.
Содержание Sigma XT Plus
Страница 1: ...Sigma XT Extinguishant Control Panel Operation and Maintenance Manual Man 1112 Issue 23 March 2016...
Страница 15: ...Man 1112 Sigma XT _23 Page 15 of 52 Detection panel terminals...
Страница 16: ...Man 1112 Sigma XT _23 Page 16 of 52 Extinguishing module terminals...
Страница 51: ...Man 1112 Sigma XT _23 Page 51 of 52...
Страница 52: ...Man 1112 Sigma XT _23 Page 52 of 52 Man 1112...