Man-1112 Sigma XT+_23
Page 47 of 52
24. Commissioning instructions
24.1 Before applying power to the panel, any solenoids or igniting actuators must be physically isolated from the
system by disconnecting both wires to it. This will prevent any accidental release of extinguishant.
24.2 When power is applied, if all connections are correct, only the green Power On indicators should be lit.
If any fault indicators are lit the wiring to the appropriate input or output should be checked an all faults
cleared before proceeding.
24.3
Once the panel is fault free, it can be configured with the desired options as
described in section 15 .
24.4
Once the panel has been configured the system should be thoroughly tested to ensure that the control
panels responds as expected and required.
24.5
After satisfactory testing, any final connections should be made (such as to the
extinguishant release actuator).
24.6
A record of the configuration options that have been set should be recorded in the tables below and this
manual provided as part of the documentation recommended by BS5839:Part 1:2002 section 40.2 b).
Detection section
CODE
FUNCTION
TICK IF SET
00
SOUNDER DELAY TIME = 30 SECONDS
01
SOUNDER DELAY TIME = 1 MINUTE
02
SOUNDER DELAY TIME = 2 MINUTES
03
SOUNDER DELAY TIME = 3 MINUTES
04
SOUNDER DELAY TIME = 4 MINUTES
05
SOUNDER DELAY TIME = 5 MINUTES
06
SOUNDER DELAY TIME = 6 MINUTES
07
SOUNDER DELAY TIME = 7 MINUTES
08
SOUNDER DELAY TIME = 8 MINUTES
09
SOUNDER DELAY TIME = 9 MINUTES
10
COMMON ALARM MODE (default)
11 TWO-STAGE
ALARM
MODE
12
ZONED ALARM MODE
21*
DISABLE FIRE BUZZER
22* DISABLE
FAULT
OUTPUT
23
DISABLE EARTH FAULT MONITORING
24
PULSED REMOTE CONTROL OUTPUT
25
ENABLE SOUNDERS ON DETECTION CIRCUITS
26
DISABLE FIRE OUTPUT
27
DO NOT CHANGE
28
INDICATE CALL POINT ACTIVATION Activation of a call point with a
270R resistance fitted is indicated
by a flashing zone indicator and
“Pu” on the 7 segment display.
Activation of a detector will be
indicated by a steady zone
indicator and nothing on the 7
segment display.
29
DO NOT RE-SOUND ALARMS FROM
ANOTHER ZONE
Silenced sounders will not re-sound
upon further zone activations.
31
ZONE 1 ALARM FROM DETECTOR DELAYED
32
ZONE 2 ALARM FROM DETECTOR DELAYED
33
ZONE 3 ALARM FROM DETECTOR DELAYED
34
ZONE 4 ALARM FROM DETECTOR DELAYED
35
ZONE 5 ALARM FROM DETECTOR DELAYED
36
ZONE 6 ALARM FROM DETECTOR DELAYED
37
ZONE 7 ALARM FROM DETECTOR DELAYED
38
ZONE 8 ALARM FROM DETECTOR DELAYED
41
ZONE 1 ALARM FROM CALL POINT DELAYED
42
ZONE 2 ALARM FROM CALL POINT DELAYED
43
ZONE 3 ALARM FROM CALL POINT DELAYED
44
ZONE 4 ALARM FROM CALL POINT DELAYED
45
ZONE 5 ALARM FROM CALL POINT DELAYED
46
ZONE 6 ALARM FROM CALL POINT DELAYED
47
ZONE 7 ALARM FROM CALL POINT DELAYED
48
ZONE 8 ALARM FROM CALL POINT DELAYED
Содержание Sigma XT Plus
Страница 1: ...Sigma XT Extinguishant Control Panel Operation and Maintenance Manual Man 1112 Issue 23 March 2016...
Страница 15: ...Man 1112 Sigma XT _23 Page 15 of 52 Detection panel terminals...
Страница 16: ...Man 1112 Sigma XT _23 Page 16 of 52 Extinguishing module terminals...
Страница 51: ...Man 1112 Sigma XT _23 Page 51 of 52...
Страница 52: ...Man 1112 Sigma XT _23 Page 52 of 52 Man 1112...