Man-1112 Sigma XT+_23
Page 29 of 52
NOTE: Setting the options marked with asterisks does not comply with EN54-2
15.2 Extinguishing modules
15.2.1 Language selection
The module is capable of displaying two languages if factory programmed to do so. The first access level 3 option
is to select the local language or the default language (English)
15.2.2 Extinguishant output mode
The Sigma XT+ module has two extinguishing outputs. These can be configured to operate together at the same
time (common) or be configured as main and reserve outputs.
The factory default setting for the extinguishing outputs is common.
To change this, switch on the enable controls keyswitch and slide the write enable switch on the module to be
configured gently to the left. Press the ENTER button on the extinguishing module. The display will show:
EXTING O/P MODE.
= COMMON
Press the ENTER button and the display will show:
EXTING O/P MODE.
= MAIN/RESERVE ?
Press the ENTER button to select main/reserve.
To save the settings, slide the write enable switch gently to the right.
When the extinguishing module is activated, only extinguishant output 1 will switch on.
There will also be an additional menu item at access level 2 to allow the reserve extinguishant output to be
selected.
CODE
FUNCTION
COMMENTS
81*
ZONE 1 NON-LATCHING
Renders the zone self-resetting so that
it can be used to receive signals from
other systems and will reset when the
input is removed.
Note: It can take up to 20 seconds for zone to reset
itself when sounders are operating
82* ZONE
2
NON-LATCHING
83* ZONE
3
NON-LATCHING
84* ZONE
4
NON-LATCHING
85* ZONE
5
NON-LATCHING
86* ZONE
6
NON-LATCHING
87* ZONE
7
NON-LATCHING
88* ZONE
8
NON-LATCHING
91
ZONE 1 DOES NOT SOUND ALARMS
Prevents the zone from operating the two common
sounder outputs.
92
ZONE 2 DOES NOT SOUND ALARMS
93
ZONE 3 DOES NOT SOUND ALARMS
94
ZONE 4 DOES NOT SOUND ALARMS
95
ZONE 5 DOES NOT SOUND ALARMS
96
ZONE 6 DOES NOT SOUND ALARMS
97
ZONE 7 DOES NOT SOUND ALARMS
98
ZONE 8 DOES NOT SOUND ALARMS
99
A1*
ZONE 1 ANY ALARM DELAYED
Zone needs to be triggered for 30 seconds continuously
before an alarm is generated.
A2*
ZONE 2 ANY ALARM DELAYED
A3*
ZONE 3 ANY ALARM DELAYED
A4*
ZONE 4 ANY ALARM DELAYED
A5*
ZONE 5 ANY ALARM DELAYED
A6*
ZONE 6 ANY ALARM DELAYED
A7*
ZONE 7 ANY ALARM DELAYED
A8*
ZONE 8 ANY ALARM DELAYED
C1
ZONE 1 SOUNDERS INHIBITED
Not used
C2
ZONE 2 SOUNDERS INHIBITED
C3
ZONE 3 SOUNDERS INHIBITED
C4
ZONE 4 SOUNDERS INHIBITED
C5
ZONE 5 SOUNDERS INHIBITED
C6
ZONE 6 SOUNDERS INHIBITED
C7
ZONE 7 SOUNDERS INHIBITED
C8
ZONE 8 SOUNDERS INHIBITED
E1*
ZONE 1 WILL NOT OPERTATE FIRE RELAY
Enables individual zones to be selected to not operate
the fire relay. This is sometimes combined with the non-
latching function to prevent ring around on
interconnected panels
E2*
ZONE 2 WILL NOT OPERTATE FIRE RELAY
E3*
ZONE 3 WILL NOT OPERTATE FIRE RELAY
E4*
ZONE 4 WILL NOT OPERTATE FIRE RELAY
E5*
ZONE 5 WILL NOT OPERTATE FIRE RELAY
E6*
ZONE 6 WILL NOT OPERTATE FIRE RELAY
E7*
ZONE 7 WILL NOT OPERTATE FIRE RELAY
E8*
ZONE 8 WILL NOT OPERTATE FIRE RELAY
Содержание Sigma XT Plus
Страница 1: ...Sigma XT Extinguishant Control Panel Operation and Maintenance Manual Man 1112 Issue 23 March 2016...
Страница 15: ...Man 1112 Sigma XT _23 Page 15 of 52 Detection panel terminals...
Страница 16: ...Man 1112 Sigma XT _23 Page 16 of 52 Extinguishing module terminals...
Страница 51: ...Man 1112 Sigma XT _23 Page 51 of 52...
Страница 52: ...Man 1112 Sigma XT _23 Page 52 of 52 Man 1112...