Man-1112 Sigma XT+_23
Page 37 of 52
16.3.4 Disable Stage 2 output
To disable the 2
nd
Stage relay output, press the UP button on the module while at access level 2 until the display
shows:
DISABLE
stage 2 output ?
Press the Enter button to select this function. The display will show:
ENABLE
STAGE 2 OUTPUT ?
The yellow disabled LED on the module that has been disabled
will be lit.
Turn the Enable keyswitch off to leave the disablement active. To re-enable the Stage 2 relay output repeat the
procedure above.
16.3.5 Disable Released output
To disable the Released relay output, press the UP button on the module while at access level 2 until the display
shows:
DISABLE
released output ?
Press the Enter button to select this function. The display will show:
ENABLE
released OUTPUT ?
The yellow disabled LED on the module that has been disabled
will be lit.
Turn the Enable keyswitch off to leave the disablement active. To re-enable the Released relay output repeat the
procedure above.
16.3.6 Disable Extract output
To disable Extract relay output, press the UP button on the module while at access level 2 until the display shows:
DISABLE
extract output ?
Press the Enter button to select this function. The display will show:
ENABLE
extract OUTPUT ?
The yellow disabled LED on the module that has been disabled
will be lit.
Turn the Enable keyswitch off to leave the disablement active. To re-enable the Extract relay output repeat the
procedure above.
16.3.7 Turn on Extract output
To turn on the extract relay output, press the DOWN button on the module while at access level 2 until the display
shows:
TURN ON
EXTRACT OUTPUT
Press the Enter button to select this function. The display will show:
TURN OFF
EXTraCT OUTPUT ?
The yellow disabled LED on the module that has been disabled
will be lit.
Turn the Enable keyswitch off to leave the Extract output active. To turn off the Extract output, repeat the
procedure above. Note: the extract output does not turn off when the module is reset.
16.3.8 Select Reserve Solenoid Output (Configuration Option)
If the extinguishing module is configured for Main/Reserve solenoid operation (See section 15.2.1) then an
additional menu option is given to select which output is used.
To turn on the Reserve Solenoid output, press the UP button on the module while at access level 2 until the
display shows:
SELECT RESERVE
EXTING. OUTPUT
Press the Enter button to select this function. The display will
show:
SELECT MAIN
EXTING. OUTPUT ?
The yellow Reserve Cylinders LED indicator on the module
will be lit.
Turn the Enable keyswitch off to leave the Reserve solenoid output active. To revert to the Main solenoid output,
repeat the procedure above.
Note: This menu option is not shown if the panel is configured to Common Solenoid mode.
Содержание Sigma XT Plus
Страница 1: ...Sigma XT Extinguishant Control Panel Operation and Maintenance Manual Man 1112 Issue 23 March 2016...
Страница 15: ...Man 1112 Sigma XT _23 Page 15 of 52 Detection panel terminals...
Страница 16: ...Man 1112 Sigma XT _23 Page 16 of 52 Extinguishing module terminals...
Страница 51: ...Man 1112 Sigma XT _23 Page 51 of 52...
Страница 52: ...Man 1112 Sigma XT _23 Page 52 of 52 Man 1112...