Man-1112 Sigma XT+_23
Page 43 of 52
19. Power supply
The control panel requires a 230V (+10%/-15%), 50/60Hz, AC mains power supply which connects to the fused
terminal block labelled “230V”.
Panels with a 3A power supply have a 20mm, F1.6A L250V mains fuse.
Panels with a 4A power supply have a 20mm T2A L250V mains fuse.
These fuses should only be replaced with fuses of the same or similar types.
The table below shows the power supply rating and recommended battery capacity for each model in the Sigma
XT+ range.
Model
Description
Power supply rating
Batteries recommended
for 24 hour standby
K21021M3
Two zone single area
3A
7Ah
K21041M3
Four zone single area
3A
7Ah
K21042M3
Four zone two area
3A
7Ah
K21081M3
Eight zone single area
3A
7Ah
K21082M3
Eight zone two area
3A
7Ah
K21083M3
Eight zone three area
4A
12Ah
K21084M3
Eight zone four area
4A
12Ah
The maximum loading on the power supply must be carefully considered when connecting externally powered
equipment such as sounders and solenoids.
Exceeding the maximum power supply rating may cause a fuse or other protective device to operate
and render the equipment inoperative until the fuse is replaced or protective devices are reset.
The tables below can be used to calculate the loading for all models by adding the loads in the second column.
K21021M3 2 zone single area
Current in milliamps
Detection section max alarm load
100
Extinguishing module max alarm load
105
Detection section total sounder load (S1&S2)
Detection section Aux 24V supply
Extinguishant module total sounder load
Extinguishant module extinguishant output load
Extinguishant module Aux 24V supply
TOTAL LOAD (must be less than 3A)
K21041M3 4 zone single area
Current in milliamps
Detection section max alarm load
210
Extinguishing module max alarm load
105
Detection section total sounder load (S1&S2)
Detection section Aux 24V supply
Extinguishant module total sounder load
Extinguishant module extinguishant output load
Extinguishant module Aux 24V supply
TOTAL LOAD (must be less than 3A)
K21042M3 4 zone two area
Current in milliamps
Detection section max alarm load
210
Extinguishing module 1 max alarm load
105
Extinguishing module 2 max alarm load
105
Detection section total sounder load (S1&S2)
Detection section Aux 24V supply
Extinguishant module 1 total sounder load
Extinguishant module 2 total sounder load
Extinguishant module 1 extinguishant output load
Extinguishant module 2 extinguishant output load
Extinguishant module 1 Aux 24V supply
Extinguishant module 2 Aux 24V supply
TOTAL LOAD (must be less than 3A)
K21081M3 8 zone single area
Current in milliamps
Detection section max alarm load
550
Extinguishing module max alarm load
105
Detection section total sounder load (S1&S2)
Detection section Aux 24V supply
Extinguishant module total sounder load
Extinguishant module extinguishant output load
Extinguishant module Aux 24V supply
TOTAL LOAD (must be less than 3A)
Содержание Sigma XT Plus
Страница 1: ...Sigma XT Extinguishant Control Panel Operation and Maintenance Manual Man 1112 Issue 23 March 2016...
Страница 15: ...Man 1112 Sigma XT _23 Page 15 of 52 Detection panel terminals...
Страница 16: ...Man 1112 Sigma XT _23 Page 16 of 52 Extinguishing module terminals...
Страница 51: ...Man 1112 Sigma XT _23 Page 51 of 52...
Страница 52: ...Man 1112 Sigma XT _23 Page 52 of 52 Man 1112...