46
Following is a table of the SIA event codes transmitted by SDACT for the different types of 7200 events.
7200
Event Word
SIA
Code
Code
Description
Restore
Code
Restore Code
Description
ALARM
P.A.S
VERIFY
CROSS ZONE
FA
or
SA
Fire Alarm
or
Sprinkler Alarm
(if a waterflow device)
FH
or
SH
Fire Alarm Restore
or
Sprinkler Alarm Restore
PRE-ALARM
ACTION
ALERT
FG Unverified
Event
– Fire
FR
Fire Restoral
OFF-NORMAL FS Fire
Supervisory
FV
Fire Supervision Restoral
SHORT
CM SHORT
DISCONNECT
MISSING
WRONG TYPE
EXTRA ADDR
CONFIG ERR
TROUBLE
LOOP BREAK
FT Fire
Trouble
FR
Fire Restoral
TEST FAIL
DIRTY
VERY DIRTY
AS
Analog Service Needed
AN
Analog Restoral
UNEXPECTED
YA
Bell Fault (Output Trouble) YH
Bell Restoral
COMM FAULT YC
Communications Fail
YK
Communications
Restoral
FAULT YX
Service
Required
YZ
Service Completed
WALK TEST
TS
Test Start
TE
Test End
ALARM TEST
FAULT TEST
BATT TEST
FIRE DRILL
RX Manual
Test
RX
Manual Test
PRGRM MODE LB
Local Program Begin
LX
Local Program End
RESET RR
Power
Up
RR
Power Up