Appendix A: Information for Receiving Station Operators
This appendix provides information on how the Point ID’s of each compatible FACP are converted to
SIA Zone numbers, and how the different types of events from each FACP are mapped to the SIA
Standard Event Codes. This information will be useful for interpreting or programming the receiving
station DACR to which the Keltron SDACT will send SIA transmissions. Note that supplementary serial
data events from compatible FACP’S will be received as ‘old’ events.
Fire Control Instruments 7100
The 7100 provides up to two Signaling Line Circuits (addressable device loops), with up to 99 Sensors
and/or 99 Modules each. These point IDs are mapped into SIA Zones 100 to 499 according to the table
below.
With the addition of INI-7100 Intelligent Network Interface Modules up to 64 7100 panels can be
networked together. SDACT supports up to 15 networked panels by placing the network node number in
the thousand’s digit of the SIA Zone. Events from the panel directly connected to SDACT, i.e. the (Local)
panel, always report on Zones in the 0100 - 0499 range. Networked panels 1 to 15 report on Zone ranges
1000 - 1499 to F000 - F499 respectively.
IMPORTANT: Please assign network node numbers in the 1 to 15 range only, and do not network
more than 15 panels. Otherwise, ambiguous SIA Zone numbers will result. Also, please verify that
the central station receiver, and central station automation computer are compatible with 4-digit
SIA Zone numbers.
3-Digit Option:
This option is available for central stations that are NOT compatible with 4-digit zone
numbers. With this option, the zone numbers are always reported in the 0100 – 0499 range. The Node
number of the networked panels, instead of being placed in the zone number thousand’s digit, is added to
the field programmed account numbers. For example, if the programmed account number is 1000, then
events from the (Local) panel report on account 1000. Events from networked panel Node 01 will report
on account 1001, and events from networked panel Node 15 will report on account 1015. The limitation
of 15 networked panels maximum still applies. Note that the 3-Digit Option must be specified when
ordering your SDACT from the factory. It is not a field configurable option. The designation “(3DO)”
will be appended to the model number on the SDACT product labeling.
The conversion rules are summarized in the following table:
CATEGORY
7100 POINT
SIA ZONE
SLC 1
L1
0100
SLC 1 Sensors
L1S01 to L1S99
0101 to 0199
SLC 1 Modules
L1M01 to L1M99 0201 to 0299
SLC 2
L2
0300
SLC 2 Sensors
L2S01 to L2S99
0301 to 0399
SLC 2 Modules
L2M01 to L2M99 0401 to 0499
Node 01 Sensor e.g.
(Node01): L1S99 1199
Node 15 Sensor e.g.
(Node15): L1S99 F199