Appendix A: Information for Receiving Station Operators 

This appendix provides information on how the Point ID’s of each compatible FACP are converted to 
SIA Zone numbers, and how the different types of events from each FACP are mapped to the SIA 
Standard Event Codes. This information will be useful for interpreting or programming the receiving 
station DACR to which the Keltron SDACT will send SIA transmissions. Note that supplementary serial 
data events from compatible FACP’S will be received as ‘old’ events. 
 

Fire Control Instruments 7100 

The 7100 provides up to two Signaling Line Circuits (addressable device loops), with up to 99 Sensors 
and/or 99 Modules each. These point IDs are mapped into SIA Zones 100 to 499 according to the table 
below. 
 
With the addition of INI-7100 Intelligent Network Interface Modules up to 64 7100 panels can be 
networked together. SDACT supports up to 15 networked panels by placing the network node number in 
the thousand’s digit of the SIA Zone. Events from the panel directly connected to SDACT, i.e. the (Local) 
panel, always report on Zones in the 0100 - 0499 range. Networked panels 1 to 15 report on Zone ranges 
1000 - 1499 to F000 - F499 respectively. 
 

IMPORTANT: Please assign network node numbers in the 1 to 15 range only, and do not network 
more than 15 panels. Otherwise, ambiguous SIA Zone numbers will result. Also, please verify that 
the central station receiver, and central station automation computer are compatible with 4-digit 
SIA Zone numbers. 
 
3-Digit Option: 

This option is available for central stations that are NOT compatible with 4-digit zone 

numbers. With this option, the zone numbers are always reported in the 0100 – 0499 range. The Node 
number of the networked panels, instead of being placed in the zone number thousand’s digit, is added to 
the field programmed account numbers. For example, if the programmed account number is 1000, then 
events from the (Local) panel report on account 1000. Events from networked panel Node 01 will report 
on account 1001, and events from networked panel Node 15 will report on account 1015. The limitation 
of 15 networked panels maximum still applies. Note that the 3-Digit Option must be specified when 
ordering your SDACT from the factory. It is not a field configurable option. The designation “(3DO)” 
will be appended to the model number on the SDACT product labeling. 
 
The conversion rules are summarized in the following table: 
 

CATEGORY

 

7100 POINT  

SIA ZONE 

SLC 1 

L1 

0100 

SLC 1 Sensors 

L1S01 to L1S99 

0101 to 0199 

SLC 1 Modules 

L1M01 to L1M99  0201 to 0299 

SLC 2 

L2 

0300 

SLC 2 Sensors 

L2S01 to L2S99 

0301 to 0399 

SLC 2 Modules 

L2M01 to L2M99  0401 to 0499 

Node 01 Sensor e.g. 

(Node01): L1S99  1199 

Node 15 Sensor e.g. 

(Node15): L1S99  F199 

 

Содержание SDACT

Страница 1: ...User s Manual for Keltron SDACT and FDACT Fire Dialers Keltron Corporation 101A First Avenue Waltham MA 02451 Voice 781 894 8710 fax 781 899 9652 SFDACT DOC Rev 2 2 11 1 06 626 2104 P N 92MSDACT...

Страница 2: ......

Страница 3: ...allation Overview 19 Selecting a Location 19 Wall Mounting 19 Field Wiring Power Supply Connections 20 Field Wiring Supervised Hardwired Alarm Zones 22 Field Wiring Power Monitor Zones 23 Field Wiring...

Страница 4: ......

Страница 5: ...is operating properly and can successfully report an alarm the fire dialer must be tested immediately after installation and periodically thereafter according NFPA 72 Chapter 10 and the enclosed test...

Страница 6: ......

Страница 7: ...nals such as fire trouble water flow or supervisory can be reliably transmitted These signals are typically provided by the general alarm general trouble etc relay contact outputs of the FACP In addit...

Страница 8: ...m and general trouble contact outputs The alarm output indicates serial port derived events that are pending transmission and input zone activations The trouble output indicates telephone line faults...

Страница 9: ...ble and alarm with 24 hour trouble resound Line seizure is provided for use with shared phone lines as allowed by the local authority having jurisdiction A manual test button is included A silence pus...

Страница 10: ...or products approved after July 23 2001 the REN for this product is part of the product identifier that has the format US AAAEQ TXXXX The digits represented by are the REN without a decimal point e g...

Страница 11: ...alarm zone inputs is required for UL Listed installations remotely monitoring FACP S via the Public Switched Telephone Network To indicate the supplementary and or redundant nature of the serial data...

Страница 12: ...CTBX Listed Signaling Device Enclosure 4 10K EOL resistors P N 64K3355 10K 2 Modular patch cords P N 63RJ4507 1 Programming utility CD P N SDSFDPrgmr 1 Printed user manual P N 92MSDACT For SDACT only...

Страница 13: ...with conduit knockouts Hinged front access door with key lock all keyed alike Size 14 H x 17 W x 4 D Weight 12 lbs Environmental specifications Relative humidity 0 to 93 non condensing Operating tempe...

Страница 14: ...zone status 4 red 4 yellow 2 Serial port status 1 red 1 yellow 4 Telephone line status 2 red 2 yellow 2 Relay output status red Audible 92 DB pulsed for alarm steady for trouble User pushbuttons 4 re...

Страница 15: ...larm relay energizes and the alarm contact active LED illuminates The audible device sounds the pulsed alarm signal The corresponding event code See appendix A is transferred to the SIA transmitter se...

Страница 16: ...eration If User Jumper J8 is installed then an off normal status change on the AC failure zone 5 will illuminate the power fault LED but the trouble relay local audible and the AC Power Failure transm...

Страница 17: ...ne line fault is detected The Telco fault LED for that line illuminates The common trouble relay energizes and the trouble contact active LED illuminates The audible device sounds the steady trouble s...

Страница 18: ...le in 24 hours if the trouble condition is still present Configuration Trouble The Keltron S FDACT stores user programmable settings in non volatile EEPROM memory The content of this memory is checked...

Страница 19: ...ow battery zone 6 or no missing battery zone 7 power monitor zone inputs If all of the power monitor zones are normal the power fault LED goes out If no other monitored conditions require the common t...

Страница 20: ...transmitter where is 1 for the primary telephone number and 2 for the secondary telephone number see dialing operation Daily Test Operation If the Keltron S FDACT is configured for 24 hour daily test...

Страница 21: ...ion DACR i e the S FDACT will pause sufficient time to receive a dial tone but does not require a dial tone to start dialing The S FDACT always dials using dual tone multi frequency DTMF tones Please...

Страница 22: ...nnect the FACP and connect the serial port to his PC or laptop While in programming mode the red and yellow serial port LEDS will alternately light once a second as an indication that programming mode...

Страница 23: ...ort SDACT only J4 should be set appropriately for the specific FACP being monitored See Serial Port Installation notes J5 J6 and J7 set the normal condition of the power monitor zones 5 6 and 7 respec...

Страница 24: ...18...

Страница 25: ...ecting a Location The Keltron S FDACT may be installed in any environment which would be comfortable for a human being Typically the S FDACT will be installed in the same room as the FACP which it is...

Страница 26: ...must include the S FDACT load current in the FACP s battery calculations Connect the 24 VDC supply making sure to observe the correct polarity Connect the positive lead to terminal 15 Connect the retu...

Страница 27: ...the PSU SPSU terminal TB1 3 or TB1 4 Using the Edwards System Technology EST2 Aux Power Output The EST2 s 24 VDC non resettable auxiliary power circuit is compatible with the S FDACT Connect S FDACT t...

Страница 28: ...llel at the monitored device Four EOLRs are provided for this purpose Keltron part number 64K3355 10K Connections to the alarm zones are as shown above Input zones are sampled every 62mS Changes must...

Страница 29: ...zones 5 6 and 7 may be used as external power source monitor input circuits Each zone is independently configurable for either normally open or normally closed dry contact programmable activation The...

Страница 30: ...lephone Line Connection The Keltron SDACT and FDACT are alarm dialing equipment and must be able to seize the telephone line and place a call in an emergency situation They must be able to do this eve...

Страница 31: ...07 Plug one end of the modular cord into the S FDACT RJ 45 jack Plug the other end into the RJ31X jack For reference proper wiring of the RJ31X jack is shown in the figure below The S FDACT is electri...

Страница 32: ...S or CTS set by J1 and J2 8 CTS or RTS set by J1 and J2 9 No connection IMPORTANT The FACP serial data connections provide supplementary alarm information only Use of the hardwired alarm zone inputs i...

Страница 33: ...ions connect the S FDACT Trouble Relay contacts to the 7100 panel by means of an FCI AMM 2 Monitor Module or equivalent The AMM 2 is an addressable dry contact monitoring module compatible with the 71...

Страница 34: ...rd electrical box adjacent to the S FDACT enclosure Connect the S FDACT Trouble Relay Normally Open contact terminal 22 to the AMM 2 violet wire Connect the S FDACT Trouble Relay Common contact termin...

Страница 35: ...CT when transmitting EST2 events Local Trouble Annunciation For on premises annunciation of S FDACT trouble conditions connect the S FDACT Trouble Relay contacts to the EST2 panel by means of a Signat...

Страница 36: ...hen transmitting MIR2 events Local Trouble Annunciation For on premises annunciation of S FDACT trouble conditions connect the S FDACT Trouble Relay contacts to the MIR2 panel by means of a Signature...

Страница 37: ...31 SDACT Field Wiring Connection Diagram...

Страница 38: ...32...

Страница 39: ...o delay 1 3 hours The S FDACT programmer is a Windows PC application SFDPrgmr exe to configure an SDACT or FDACT for use The S FDACT programmer is compatible with Windows XP Windows 2000 Windows NT an...

Страница 40: ...Trouble Restore Power Monitor Tab As shown in the figure below the power monitor tab is used to set the event codes for the three unsupervised power monitor zones The AC power monitor input zone 5 has...

Страница 41: ...manual test Set Telephone Numbers These boxes are used to set the primary and secondary telephone numbers that S FDACT will dial when reporting Both must be set before uploading the configuration to t...

Страница 42: ...Set Options Telephone Lines Used The default setting is for S FDACT to use and supervise both of its telephone line connections If a second telephone line is not available checking the line 1 only opt...

Страница 43: ...sync time mode and any values you entered for the date and time will be overwritten by current values from your PC s clock Set Date and Set Time Use these boxes to manually set the date and time to be...

Страница 44: ...en a previously saved S FDACT configuration file Save Saves the current configuration settings to the previously opened file If no file was opened previously it displays a standard Windows file save a...

Страница 45: ...8 After the S FDACT has reported the zone restore to normal the S FDACT should return to the idle all normal state Troubleshooting In case of trouble Check for the proper power input with sufficient v...

Страница 46: ...n Corporation 101A First Avenue Waltham Massachusetts 02451 Telephone 781 894 8710 Toll Free 800 966 6123 FAX 781 899 9652 Email info keltroncorp com GENERAL Telephone 781 894 8710 Email info keltronc...

Страница 47: ...improper installation or application The warranty does not extend to products that have been repaired or altered outside our factory without our written approval Except as provided above Keltron Corpo...

Страница 48: ...42...

Страница 49: ...only and do not network more than 15 panels Otherwise ambiguous SIA Zone numbers will result Also please verify that the central station receiver and central station automation computer are compatibl...

Страница 50: ...FV Fire Supervision Restoral MLT EVENTS UA Untyped Zone Alarm UH Untyped Alarm Restore SHORT DISCONNECT MISSING WRONG TYPE EXTRA ADDR CONFIG ERR LOOP BREAK FT Fire Trouble FR Fire Restoral TEST FAIL...

Страница 51: ...added to the field programmed account numbers For example if the programmed account number is 1000 then events from unit number 1 ALU1 QZU1 EZU1 report on account 1000 Events from unit number 2 will...

Страница 52: ...ORMAL FS Fire Supervisory FV Fire Supervision Restoral SHORT CM SHORT DISCONNECT MISSING WRONG TYPE EXTRA ADDR CONFIG ERR TROUBLE LOOP BREAK FT Fire Trouble FR Fire Restoral TEST FAIL DIRTY VERY DIRTY...

Страница 53: ...No conversion is necessary for the detectors modules and notification appliance circuit point IDs Those point IDs are transmitted directly as the 4 digit SIA zone number The EST2 panel fault point ID...

Страница 54: ...RVISORY FS Fire Supervisory FV Fire Supervision Restore SHORT FAULT OPEN FAULT FT Fire Trouble FR Fire Restoral OPEN FAULT Battery YT System Battery Trouble YR System Battery Restoral OPEN FAULT Prima...

Страница 55: ...is necessary for the detectors modules and notification appliance circuit point IDs Those point IDs are transmitted directly as the 4 digit SIA zone number The MIR2 panel fault point IDs are converted...

Страница 56: ...RVISORY FS Fire Supervisory FV Fire Supervision Restore SHORT FAULT OPEN FAULT FT Fire Trouble FR Fire Restoral OPEN FAULT Battery YT System Battery Trouble YR System Battery Restoral OPEN FAULT Prima...

Страница 57: ...CW Was Force Armed CX Custom Function Executed CZ Point Closing DA Card Assigned DB Card Deleted DC Access Closed DD Access Denied DE Request to Enter DF Door Forced DG Access Granted DH Door Left Op...

Страница 58: ...ld JO Log Overflow JP User On Premises JR Schedule Executed JS Schedule Changed JT Time Changed JV User Code Changed JX User Code Deleted JY User Code Added JZ User Level Set KA Heat Alarm KB Heat Byp...

Страница 59: ...Alarm SB Sprinkler Bypass SC Change of State SH Sprinkler Alarm Restore SJ Sprinkler Trouble Restore SR Sprinkler Restoral SS Sprinkler Supervisory ST Sprinkler Trouble SU Sprinkler Unbypass TA Tamper...

Страница 60: ...Trouble YE Receiver Line Card Restored YF Parameter Checksum Fail YG Parameter Changed YH Bell Restored YI Overcurrent Trouble YJ Overcurrent Restore YK Communications Restoral YM System Battery Missi...

Отзывы: