defaults. While this box is checked, you can view the event codes by clicking on the various tabs, but you
cannot modify them. To change any event codes, first click on the ‘Use Default Event Codes:’ box so it is
unchecked. Clicking the box again will reset all codes to the factory defaults. See Appendix B for a list of
the defined standard SIA event codes.
Zone Tabs
As shown in the figure above, the zone 1 through zone 4 tabs are used to set the event codes for the four
EOLR-supervised alarm zones. You can set the codes for alarm, trouble, and their respective restores. The
factory default codes for each zone are:
FA
“Fire
Alarm”
FT
“Fire
Trouble”
FH
“Fire
Alarm
Restore”
FJ
“Fire Trouble Restore”
Power Monitor Tab
As shown in the figure below, the power monitor tab is used to set the event codes for the three,
unsupervised power monitor zones.
The AC power monitor input (zone 5) has a programmable fault code and restore code. The low battery
input (zone 6) and the missing battery input (zone 7) each have a programmable fault code, but there is a
common restore code. The factory default codes are:
YP
“Power Supply Trouble”
YT
“System Battery Trouble”
YQ
“Power Supply Restore”
YM
“System Battery Missing”
YR
“System Battery Restore”
Telephone Lines Tab
As shown in the figure below, the telephone lines tab is used to set the event codes for line and
communication faults, and their respective restores for the two telephone line connections.
The factory default codes are:
LT
“Phone Line Trouble”
YS
“Communications Trouble”
LR
“Phone Line Restore”
YK “Communications
Restore”