Preface
The information contained in this manual will enable a trained alarm technician to properly install,
configure, connect, program, power up, test, and commission the Keltron S/FDACT family of fire dialers.
We encourage you to read this entire manual before you apply power to your unit.
To ensure proper operation, S/FDACT fire dialers must be installed in accordance with the National Fire
Alarm Code (NFPA 72), the National Electrical Code (NFPA 70), and according to the enclosed
installation instructions.
To verify that the S/FDACT fire dialer is operating properly and can successfully report an alarm, the fire
dialer must be tested immediately after installation, and periodically thereafter, according NFPA 72
Chapter 10, and the enclosed test instructions.
Note: System Re-acceptance Test after Software Changes: To ensure proper system operation, this
product must be tested in accordance with NFPA 72 Chapter 10 after any programming operation or
change in site-specific software. Re-acceptance testing is required after any change, addition or deletion
of system components, or after any modification, repair or adjustment to system hardware or wiring.
IMPORTANT:
A solid connection to a local Earth Ground is required per the FCC to protect the
telephone line circuits from electrical surges.