44
Following is a table of the SIA event codes transmitted by SDACT for the different types of 7100 events.
7100
Event Word
SIA
Code
Code
Description
Restore
Code
Restore Code
Description
FIRST ALARM
ALARM
P.A.S
VERIFY
FA
or
SA
Fire Alarm
or
Sprinkler Alarm
( if a waterflow device)
FH
or
SH
Fire Alarm Restore
or
Sprinkler Alarm Restore
ACTION
ALERT
FG Unverified
Event
– Fire
FR
Fire Restoral
OFF-NORMAL FS Fire
Supervisory
FV
Fire Supervision Restoral
MLT EVENTS
UA
Untyped Zone Alarm
UH
Untyped Alarm Restore
SHORT
DISCONNECT
MISSING
WRONG TYPE
EXTRA ADDR
CONFIG ERR
LOOP BREAK
FT Fire
Trouble
FR
Fire Restoral
TEST FAIL
DIRTY
VERY DIRTY
AS
Analog Service Needed
AN
Analog Restoral
OUTPT FAIL
YA
Bell Fault (Output Trouble) YH
Bell Restoral
AC FLT TO
AT
AC Trouble
AR
AC Restoral
FAULT
TALLY FLT
EEPROM BAD
YX Service
Required
YZ
Service Completed
WALK TEST
TS
Test Start
TE
Test End
ALARM TEST
SPVSN TEST
FAULT TEST
FIRE DRILL
RX Manual
Test
RX
Manual Test
PRGRM MODE LB
Local Program Begin
LX
Local Program End
RESET RR
Power
Up
RR
Power Up