45
Monitoring and analysis parameters
No.
Name
r/w Enter based on
CP.07
peak DC utilization
–
–
ru.14
Resolution
Meaning
1 %
Parameter CP.07 enables to recognize short-term peak utilization with-
in an operating cycle. For that the highest value of CP.06 is stored in
CP.07. The peak value memory can be cleared by pressing the UP and
DOWN key or via bus by writing any value you like to the address of
CP.07. Switching off COMBIVERT R6-N also clears the memory.
No.
Name
r/w Enter based on
CP.08
DC current
–
–
ru.15
Resolution
Meaning
0.1 A
Display of the actual DC output current in ampere.
No.
Name
r/w Enter based on
CP.09
DC voltage
–
–
ru.19
Resolution
Meaning
1 V
Display of actual DC link voltage in volt. The value is measured at the
DC output terminals of the COMBIVERT R6-N.
No.
Name
r/w Enter based on
CP.10
peak DC voltage
–
–
ru.20
Value range
Meaning
0…1000 V
Parameter CP.10 enables to recognize voltage peaks within an oper-
ating cycle. For that the highest value of CP.09 is stored in CP.10. The
peak value memory can be cleared by pressing the UP and DOWN key
or via bus by writing any value you like to the address of CP.10. Switch-
ing off COMBIVERT R6-N also clears the memory.
No.
Name
r/w Enter based on
CP.11
power module temperature
–
–
ru.38
Resolution
Meaning
1 °C
Display of the actual power module temperature. On exceeding the
maximum power module temperature (see "Technical data") the mod-
ulation is switched off and error E.OH is displayed. Message E.nOH is
displayed after the cooling period. The error can be reset now.