28
Connection of the COMBIVERT R6-N
Type A1: AC/DC inverter
Type B1: AC inverter
Type C1: DC inverter
+
++
--
L1
L2
L3
+PA
-
L1
L2
L3
+
or also type D1
+PA
-
L1
L2
L3
+
+
++
--
Type A2: AC/DC inverter
Type B2: AC inverter
Type C2: DC inverter
+
++
--
L1
L2
L3
+PA
-
L1
L2
L3
+
+
++
--
This type can be supplied
by mains and by DC circuit.
The starting current limita-
tion is designed after the
input terminals. When used
as output parallel connected
inverters must have an own
starting current limiting at
the DC voltage input. The
maximum charging current is
taken into account.
This type can be supplied
by mains. The DC terminals
can be used as output with
regard to the maximum DC
link capacity. When used as
input ensure that the starting
current is externally limited.
This type is only a DC in-
verter with starting current
limiting. The DC inverter
can be combined with all
other types in consideration
of the maximum DC link
capacity.
Figure 11: General description of input terminals at KEB inverter