43
Password input
5.4
Password input
No.
Name
r/w Enter based on
CP.00
password input
–
–
Ud.01
Ex works the COMBIVERT R6-N is supplied without password protection, i.e. all changea-
ble parameters can be adjusted. After parameterizing the inverter can be secured against
unauthorized access (locking: 100 and release: 200). The adjusted mode is stored.
5.5
Monitoring and analysis parameters
The following parameters serve for the functional monitoring during operation.
No.
Name
r/w Enter based on
CP.01
inverter state
–
–
ru.00
The status display shows the actual working condition of the COMBIVERT.
Status messages
rEGEn Regeneration active (regenerative operation)
bbL
Count down of the base-block time, R6-N released
noP
„no Operation“ control release not bridged, modulation switched off
nEtoF
Mains power failure; regenerative operation is further possible, if the disconnect-
ing time E.nEt (Pn.14) > 0 s
rinit
Re-initialisation
Stb
R6-N regenerative unit in stand-by operation (motor operation)
Error Messages
E.EF
External Fault, error message by an external unit
E.FnEt
„Error! Mains frequency", the mains frequency deviates more than 5 %. The max.
mains frequency deviation can be adjusted in the application mode with CS.03.
E.Frlr
Error "Fault reset level reached" is triggered when the adjusted value in parameter
Pn.15 is reached within one hour. The error can be reset.
E.LSF
Error! Charging circuit, load-shunt defective or wrong or input voltage too low. This
message is displayed for a short time during the power-on phase (no error mes-
sage follows).
E.nEt
„Error! net, one or more phases are missing
E.nOH No overheat, over-temperature error not present (E.OH), error can be reset.
E.nOL
No overload, cooling time after E.OL is up , error can be reset.
E.OC
„Error! Overcurrent“, output current too high or ground fault
E.OH
„Error! Overtemperature“, overheating at heat sink (see „Technical data“)
E.OHI
„Error! Interior temperature“, temperature in the interior > 95 °C
E.OL
„Error! Overload“, overload monitoring of the regenerative unit has responded
E.OP
„Error! Overvoltage“, DC link voltage too high
E.Pu
„Error in power unit“, power unit code is missing, load shunt relay defective
continued on the next page