30
Connection of the COMBIVERT R6-N
Housing Size E
Name
Tightening torque [Nm]
- -
++
L12
++
L32
L22
- -
permissible line cross section
max.
4
Function
1.5…25 mm²
(AWG 16…4)
L12
L22
L32
3-phase supply input of
the commutation reactor
++
- -
DC voltage output with
starting current limiting
PE,
Connection for shield-
ing/grounding occurs
via provided copper bar
by clamping yoke or
ring cable lug. It must
be mounted with four
screws at the heat sink.
–
3
Strain
relief,
shield-
ing
The strain relief and the
shielding must be done
by the customer e.g.
with two clips.
-
3
Figure 13: Terminals / earth handle
4.3.3
Terminals commutation reactor/ harmonic filter
15 / 19Z1B04-1000 (commutation
reactor)
15 / 19Z1C04-1000 (harmonic filter)
Name
Tightening torque [Nm]
PE
PE
L1.1
L.2.1 L3.1
L1.2
L2.2
L3.2
permissible line cross section
Size 15
1.2…2
Function
Size 15
2.5...16 mm²
(AWG 20…6)
Size 19
2.5...35 mm²
(AWG 12…2)
L1.1
L2.1
L3.1
3-phase mains connection
Size 19
2,5...5
L1.2
L2.2
L3.2
Output to COMBIV-
ERT R6-N
PE
Connection for shield-
ing/earthing
–
6
Figure 14:
Terminals for commutation reactor / harmonic filter