Regenerative adjustments
© KEB, 2008-02
COMBIVERT R6-S
Page 3.5 - 3
3
10
3.5 Regenerative adjustments
3.5.1 Operating mode
Operating mode
Pn.19 determines :
- if the unit is a master or a slave
- Unit is operated with commutation choke or
harmonic filter
Commutation choke
Advantages
Disadvantages
·
cheap purchase
·
only for area of industry
Harmonic filter
Advantages
Disadvantages
·
sine-wave regeneration
·
high purchase cost
Pn.19: Operating mode
Value
Default
Note
0:
Master with commutation choke
X
For high power regenerative units can be parallel con-
nected.
Here, a device must be specified as master. All further are
adjusted as slave. Single units are alwags master.
The coupling of the regenerative units is made by termi-
nals X2A.16/18, since this is a fast digital input.
1: Master with harmonic filter
2:
Slave with commutation choke
3: Slave with harmonic filter
If R6 units of different size are parallel connected, it is recommended, to
define the larger unit as ma
-
ster.
With changing of the adjustment of Pn.19 the parameterizing of cS.00, cS.01 and cS.04 for the KEB standard
commutation choke or the KEB standard
harmonic filter is preset. When using KEB products no further pa
-
rameter setting is necessary. The values of cS.00, cS.01 and cS.04 are overwritten at external products with
response of Pn.19.
If the R6 is operated as a master, I4 (X2A.16) is automatically configured as digital
output, if the R6 is operated
as a slave, X2A.16 configured as digital
input.
3.5.2 Setting of the choke rating data or harmonic filter
The regenerative unit calculates the voltage losses at the input with the following two parameters. The parame-
ters are preset with parameter Pn.19.
Parameter
Addr.
R PG E Min. value Max. value Res. [?] Default
cS.00 Choke/ rated voltage
0F00h rw
-
-
0
1000
1
V
var
Setting in accordance with the
data sheet of the choke respectively harmonic filter. The default value is 0 at
the power adapted harmonic filter.
Parameter
Addr.
R PG E Min. value Max. value Res. [?] Default
cS.01 Choke / rated current
0F01h rw
-
-
0
5000
1
A
var
Setting in accordance with the
data sheet of the choke respectively harmonic filter.
Содержание combivert R6-S
Страница 1: ...APPLICATION MANUAL Mat No Rev 00R6SEA K130 1 A GB KEB COMBIVERT R6 S Version 1 3 ...
Страница 2: ...Page 1 1 2 COMBIVERT R6 S KEB 2008 02 Introduction ...
Страница 4: ...Page 1 1 4 COMBIVERT R6 S KEB 2008 02 Introduction ...
Страница 14: ...Page 1 2 6 COMBIVERT R6 S KEB 2008 02 Product overview ...
Страница 28: ...Page 2 1 6 COMBIVERT R6 S KEB 2008 02 Fundamentals ...
Страница 34: ...Page 2 2 6 COMBIVERT R6 S KEB 2008 02 Password structure ...
Страница 40: ...Page 3 1 2 COMBIVERT R6 S KEB 2008 02 Parameter overview 3 1 1 Parameter list F5 A E and H 3 1 3 ...
Страница 116: ...Page 3 8 2 COMBIVERT R6 S KEB 2008 02 Special functions 3 8 1 Program timer counter 3 8 3 ...
Страница 130: ...Page 3 9 10 COMBIVERT R6 S KEB 2008 02 Define CP Parameters ...
Страница 140: ...Page4 2 2 COMBIVERT R6 S KEB 2008 02 Start up ...
Страница 144: ...Page4 2 6 COMBIVERT R6 S KEB 2008 02 Start up ...
Страница 146: ...Page 5 1 2 COMBIVERT R6 S KEB 2008 02 Error assistance 5 1 1 General 5 1 3 5 1 2 Error messages and their causes 5 1 3 ...
Страница 150: ...Page 5 1 6 COMBIVERT R6 S KEB 2008 02 Error assistance ...
Страница 158: ...Page 6 1 8 COMBIVERT R6 S KEB 2008 02 Project design ...
Страница 160: ...Seite 7 1 2 COMBIVERT R6 S KEB 2008 02 Annex 7 1 1 Keyword index 7 1 3 ...
Страница 166: ......
Страница 167: ......