Protective functions
© KEB, 2008-02
COMBIVERT R6-S
Seite 3.6 - 7
3
10
3.6.1.10
Regeneration error
Error Messages
E.nEt
"Error! Mains", one or more phases are missing
E.SYn
"Error! Synchronization", phase allocation at commutation choke not correct
Parameter
Adr.
R PG E Min.value Max.value Res. [?] Default
cS.03 Mains frequency max. tolerance 0F03h rw
-
-
0
5
1
%
5
Adjustment of the max. frequency tolerance.
3.6.2 Response to malfunction messages
3.6.2.1 Selection of the response
Abnormal stopping (i.e. automatic shutdown of the drive) is possible for all errors that do not enforce immediate
shutdown of the modulation or for which pre-warnings can be generated.
If abnormal stopping is reasonable in the application, the possibility to set a digital output is available for many
malfunctions.
The response is programmable for the following malfunctions:
- Ext. error
Pn.03 Reaction to external fault
- Watchdog
Pn.05 E.bus stopping mode
- Set selection error
Pn.18 E.Set stopping mode
Other errors switch off the modulation, but a pre-warning can be generated prior to their triggering. In the time
between the pre-warning signal and the triggering of the error, the drive can be stopped. The response is pro-
grammable:
- overload
Pn.08 warning OL stop mode
- Heat sink overtemperature
Pn.10 Heat sink overtemperature response
- internal overtemperature
Pn.16 Internal overtemperature response
The descriptions of the errors and the corresponding pre-warning signals are contained in chapter 5.1 „Error
assistance“.
The following responses can be used for all malfunctions and errors, respectively:
Pn.03, Pn.05, Pn.08, Pn.10, Pn.12, Pn.14, Pn.16, Pn.18: Reaction
Value
Description
0: error / no auto
restart
the malfunction turns into the error (
Status: E.xx), immediate shutdown of the
modulation, restart only after RESET
3: Modulation off / auto
restart
Immediate shutdown of the modulation, automatic restart as soon as the mal-
function is resolved
6: no error
malfunction deactivated
Pn.08, Pn.10, Pn.14
Value
Description
6: Warning via
digital output
No response of the drive, the malfunction (and pre-warning, respectively ) can be issu-
ed via a digital output.
Содержание combivert R6-S
Страница 1: ...APPLICATION MANUAL Mat No Rev 00R6SEA K130 1 A GB KEB COMBIVERT R6 S Version 1 3 ...
Страница 2: ...Page 1 1 2 COMBIVERT R6 S KEB 2008 02 Introduction ...
Страница 4: ...Page 1 1 4 COMBIVERT R6 S KEB 2008 02 Introduction ...
Страница 14: ...Page 1 2 6 COMBIVERT R6 S KEB 2008 02 Product overview ...
Страница 28: ...Page 2 1 6 COMBIVERT R6 S KEB 2008 02 Fundamentals ...
Страница 34: ...Page 2 2 6 COMBIVERT R6 S KEB 2008 02 Password structure ...
Страница 40: ...Page 3 1 2 COMBIVERT R6 S KEB 2008 02 Parameter overview 3 1 1 Parameter list F5 A E and H 3 1 3 ...
Страница 116: ...Page 3 8 2 COMBIVERT R6 S KEB 2008 02 Special functions 3 8 1 Program timer counter 3 8 3 ...
Страница 130: ...Page 3 9 10 COMBIVERT R6 S KEB 2008 02 Define CP Parameters ...
Страница 140: ...Page4 2 2 COMBIVERT R6 S KEB 2008 02 Start up ...
Страница 144: ...Page4 2 6 COMBIVERT R6 S KEB 2008 02 Start up ...
Страница 146: ...Page 5 1 2 COMBIVERT R6 S KEB 2008 02 Error assistance 5 1 1 General 5 1 3 5 1 2 Error messages and their causes 5 1 3 ...
Страница 150: ...Page 5 1 6 COMBIVERT R6 S KEB 2008 02 Error assistance ...
Страница 158: ...Page 6 1 8 COMBIVERT R6 S KEB 2008 02 Project design ...
Страница 160: ...Seite 7 1 2 COMBIVERT R6 S KEB 2008 02 Annex 7 1 1 Keyword index 7 1 3 ...
Страница 166: ......
Страница 167: ......