Protective functions
© KEB, 2008-02
COMBIVERT R6-S
Seite 3.6 - 3
3
10
3.6 Protective functions
The protective functions protect the regenerative unit against switching off caused by overcurrent, overvoltage
as well as thermal overheating. Furthermore, you can restart the drive after an error automatically (Keep-On-
Running).
3.6.1 Error and warning messages
For diagnostic purposes, the regenerative unit displays different malfunction- and error messages. Errors are
all those events that trigger an immediate switching off of the modulation, malfunctions allow a defined re
-
sponse.
For some events (ext. error, bus monitor response), one can decide in the programming whether this is an error
or a malfunction.
For some errors, e.g., the overload error, a pre-warning can be generated. This pre-warning is treated like a
malfunction, i.e., the appropriate response to the pre-warning is programmable.
Example 1 (Error):
The regenerative unit detects overcurrent and raises the error. Display in parameter
ru.00: „Error! Overcurrent“
(E.OC). Since this error cannot be predicted, there is no possibililty of a pre-warning. The modulation is swit-
ched off immediately.
Example 2 (operating condition programmed as error):
The reaction of the bus monitor („watchdog“) shall trigger an error. Programming Pn.05: „Watchdog response“ =
0 (error / no auto restart). Display in parameter
ru.00: „Error! Watchdog“ (E.buS). If a digital output is program
-
med on a fault signalling relay, the relay switches.
Beispiel 3 (operating condition programmed as malfunction):
The reaction of the bus monitor („watchdog“) shall trigger a malfunction. Programming
Pn.05: „Watchdog re
-
sponse“ = 0 (error / no auto restart). Display in parameter
ru.00: „Error! Watchdog“ (E. buS). If a digital output
is programmed on a fault signalling relay, the relay does not switch by fault.
If the digital output shall also respond to malfunctions, switching condition 6 „abnormal stopping / error“ must
be used. Alternatively, Pn.65 can be adjusted so that a malfunction is treated like an error with respect to the
status displays and the digital outputs.
Example 4 (pre-warning):
If the heat sink temperature exceeds a limit (dependent on the unit type), the modulation is switched off, the
unit raises an error. With Pn.11 „heat sink overtemperature warning level“ a temperature can be set at which a
pre-warning is generated.
Desired response: when exceeding the temperature of
Pn.11 the unit switches off the modulation. When the
heat sink temperature decreases again, an automatic restart shall occur.
Programming Pn.10 „warning OH stop. mode“ = 3 (modulation off/ auto restart).
Display in parameter
ru.00: „Warning! Heat sink temperature“ (A.OH).
After decreasing the temperature the unit carry out an automatic restart. If, however, the heat sink temperature
continues to rise and exceeds the error limit, the COMBIVERT raises an „Error! Heat sink temperature“ (E.
OH).
Содержание combivert R6-S
Страница 1: ...APPLICATION MANUAL Mat No Rev 00R6SEA K130 1 A GB KEB COMBIVERT R6 S Version 1 3 ...
Страница 2: ...Page 1 1 2 COMBIVERT R6 S KEB 2008 02 Introduction ...
Страница 4: ...Page 1 1 4 COMBIVERT R6 S KEB 2008 02 Introduction ...
Страница 14: ...Page 1 2 6 COMBIVERT R6 S KEB 2008 02 Product overview ...
Страница 28: ...Page 2 1 6 COMBIVERT R6 S KEB 2008 02 Fundamentals ...
Страница 34: ...Page 2 2 6 COMBIVERT R6 S KEB 2008 02 Password structure ...
Страница 40: ...Page 3 1 2 COMBIVERT R6 S KEB 2008 02 Parameter overview 3 1 1 Parameter list F5 A E and H 3 1 3 ...
Страница 116: ...Page 3 8 2 COMBIVERT R6 S KEB 2008 02 Special functions 3 8 1 Program timer counter 3 8 3 ...
Страница 130: ...Page 3 9 10 COMBIVERT R6 S KEB 2008 02 Define CP Parameters ...
Страница 140: ...Page4 2 2 COMBIVERT R6 S KEB 2008 02 Start up ...
Страница 144: ...Page4 2 6 COMBIVERT R6 S KEB 2008 02 Start up ...
Страница 146: ...Page 5 1 2 COMBIVERT R6 S KEB 2008 02 Error assistance 5 1 1 General 5 1 3 5 1 2 Error messages and their causes 5 1 3 ...
Страница 150: ...Page 5 1 6 COMBIVERT R6 S KEB 2008 02 Error assistance ...
Страница 158: ...Page 6 1 8 COMBIVERT R6 S KEB 2008 02 Project design ...
Страница 160: ...Seite 7 1 2 COMBIVERT R6 S KEB 2008 02 Annex 7 1 1 Keyword index 7 1 3 ...
Страница 166: ......
Страница 167: ......