Page 3.8 - 4
COMBIVERT R6-S
© KEB, 2008-02
Special functions
Timer / Mode (LE.21 / LE.26)
LE.21 and LE.26 determine the clock source and the counting direction of timer 1 and 2. Clock pulse source can
be the time counter in 0.01s or 0.01h grid, pulses from a digital input. The timer runs generally as long as a star-
ting condition is active. After a reset the timer starts again at zero. Following clock sources can be selected:
LE.21 / LE.26: Timer 1 / 2 Mode
Bit
Meaning
Value
Explanation
0...2 Selection clock
pulse source
0: 0,01s (internally clock)
The timer value increases / decreases every 10 ms by
0.01.
1: 0,01h (internally
clock)
The timer value increases / decreases every 36s by
0.01.
2: every slope T1-I3 /
T2-I4
Each slope on I3 (for timer 1) or I4 (for timer 2) incre-
ases / decreases the timer value by 0.01.
3: positive slope T1-I3 /
T2-I4
A rising slope on I3 (for timer 1) or I4 (for timer 2) incre-
ases / decreases the timer value by 0,01.
4...7: reserved
3, 4 Counting direc-
tion
0: Upward
The counting direction of the timer is always upwards
24:downwards
Timer / start condition (LE.18 / LE.23)
The conditions when the timer is started can be selected from the following table. The individual conditions are
OR-operated with the timer start input selection (LE.17/ LE.22).
LE.18 / LE.23: Timer / Starting condition
Bit
Value Timer / Starting condition
0
1
Modulation on
1
2
Modulation off
In case of several starting conditions the values are to be added up.
Timer start input selection (LE.17 / LE.22)
Additionally the timer can be activated by one or several inputs. The sum of the valences is to be entered, if
the timer shall be started by different inputs The individual inputs are OR-operated. The start input selection is
OR-operated with the timer / starting condition (LE.18 / LE.22).
Содержание combivert R6-S
Страница 1: ...APPLICATION MANUAL Mat No Rev 00R6SEA K130 1 A GB KEB COMBIVERT R6 S Version 1 3 ...
Страница 2: ...Page 1 1 2 COMBIVERT R6 S KEB 2008 02 Introduction ...
Страница 4: ...Page 1 1 4 COMBIVERT R6 S KEB 2008 02 Introduction ...
Страница 14: ...Page 1 2 6 COMBIVERT R6 S KEB 2008 02 Product overview ...
Страница 28: ...Page 2 1 6 COMBIVERT R6 S KEB 2008 02 Fundamentals ...
Страница 34: ...Page 2 2 6 COMBIVERT R6 S KEB 2008 02 Password structure ...
Страница 40: ...Page 3 1 2 COMBIVERT R6 S KEB 2008 02 Parameter overview 3 1 1 Parameter list F5 A E and H 3 1 3 ...
Страница 116: ...Page 3 8 2 COMBIVERT R6 S KEB 2008 02 Special functions 3 8 1 Program timer counter 3 8 3 ...
Страница 130: ...Page 3 9 10 COMBIVERT R6 S KEB 2008 02 Define CP Parameters ...
Страница 140: ...Page4 2 2 COMBIVERT R6 S KEB 2008 02 Start up ...
Страница 144: ...Page4 2 6 COMBIVERT R6 S KEB 2008 02 Start up ...
Страница 146: ...Page 5 1 2 COMBIVERT R6 S KEB 2008 02 Error assistance 5 1 1 General 5 1 3 5 1 2 Error messages and their causes 5 1 3 ...
Страница 150: ...Page 5 1 6 COMBIVERT R6 S KEB 2008 02 Error assistance ...
Страница 158: ...Page 6 1 8 COMBIVERT R6 S KEB 2008 02 Project design ...
Страница 160: ...Seite 7 1 2 COMBIVERT R6 S KEB 2008 02 Annex 7 1 1 Keyword index 7 1 3 ...
Страница 166: ......
Страница 167: ......