GB - 8
2.3
Technical data
2.3.1 230 V class
Product Description
Inverter size
13
14
Housing size
E
E
Phases
3
3
Output rated power
[kVA]
9.5
13
Max. rated motor power
[kW]
5.5
7.5
Output rated current
[A]
24
33
Output rated current UL
[A]
22
28
Max. short time current
[A]
36
49.5
OC-tripping current
[A]
43
59
Rated input current
[A]
31
43
Rated input current UL
[A]
28
36
Max. permissible main fuse type gG
[A]
35
50
Rated switching frequency
[kHz]
8
4
Max. switching frequency
[kHz]
16
16
Power dissipation at nominal operating
[W]
290
350
Power dissipation at DC operating
[W]
265
300
Minimum braking resistor
[Ω]
16
16
Maximal braking current
[A]
25
25
Rated input voltage
[V]
230 (UL: 240)
Input voltage range U
in
[V]
180…260 ±0
Mains frequency
[Hz]
50…60 ±2
output voltage
[V]
3 x 0…U
in
Output frequency
1)
[Hz]
0…400
Max. motor line length (shielded)
[m]
100
For use in USA
Max. mains fuse type RK5
[A]
40
50
Max. input fusing MMC type "E"
[A]
40
45
1) The actual output frequency is depending on the parameterisation. The output frequency is to be limited in such
way that 1/10 of the switching frequency is not exceeded. Output frequencies above 599 Hz are possible by
changing the operating mode at control type „BASIC“ (xxF5Bxx-xxxx) as well as for special devices on request.
This devices are subject to export authorisation according to entry 3A225 Annex I of the Dual-Use Regulation
and they are labeled accordingly on the delivery note. The output frequency is limited to max. 599 Hz for all other
control types. This devices are not subject to export authorisation.
With input rated voltage of 480 Vac no braking resistor shall be connected at control type "BASIC". The
operating threshold of the braking resistor (Pn.69) must be adjusted at least to 770 Vdc for all other
controls (see annex).
Site altitude maximal 2000 m above sea level. With site altitudes over 1000 m a derat-
ing of 1 % per 100 m must be taken into consideration.