GB - 24
CP-Parameter
dulation is switched off!
CP.29 Analog output 1 / Function
CP.29 defines the function of analog output 1.
Value Function
Scaling factor
0…100 % (0…±100 %)
0
Absolute actual frequency CP.3
0…100 Hz
1
absolute set frequency CP.2
0…100 Hz
2
actual frequency CP.3
0…±100 Hz
3
set frequency CP. 2
0…±100 Hz
4
output voltage CP.9
0…500 V
5
DC link voltage CP.7
0…1000 V
6
apparent current CP.4
0…2 • rated current
7
active current ru.17
0…2 • ±rated current
8…10 only application mode
11
absolute active current ru.17
0…2 • rated current
12
power stage temperature ru.38
0…100 °C
13
motor temperature ru.46
0…100 °C
14…18 only application mode
19
ramp output frequency ru.2
0…±100 Hz
20
absolute ramp output frequency ru.2
0…100 Hz
CP.31 Relay output 1 / function (terminals X2A.24...26)
CP.32 Relay output 2 / function (terminals X2A.27...29)
The switching level of CP.31 is pre-set to 100,00.
The switching level of CP.32 is adjusted by CP.33!
Va-
lue
Function
0
No function (generally off)
1
Generally on
2
Run signal; also by DC-braking
3
Ready signal (no error)
4
Fault relay
5
Fault relay (without auto-reset)
6
Warning or error message at abnormal stopping
7
Overload pre-warning
8
Overtemperature alert signal power stage
9
External Overtemperature alert signal motor
11 Overtemperature alert signal interior OHI
12 Cable breakage 4...20 mA on analog input 1
14 max. constant current (Stall, CP.25) exceeded
15 max. ramp current (LA-Stop, CP.24) exceeded
16 DC-braking active
20 Actual value = set value (CP.3 = Fcon; rcon; not at noP, LS, error, SSF)
21 Accelerate (CP.3=FAcc, rAcc, LAS)
22 Decelerate (CP.3 = FdEc, rdEc, LdS)
23 Real direction of rotation = set direction of rotation
24 Utilization (CP.6) > switching level