V6R VRF 50Hz
Part 2 - Out
door Unit Engineering Da
ta
Mini Amazon III Series
77
Table 2-7.8: KMF-120 DVN4 heating capacity
Combination (%) (Capacity
index)
Outdoor temperature
(°C DB)
Indoor temperature(°C WB)
16.00
18.00
20.00
21.00
22.00
24.00
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
°C DB
°C WB
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
130%
-13.7
-15
11.92
2.87
11.88
2.95
11.83
3.07
11.83
3.15
11.79
3.23
11.75
3.28
-11.8
-13
12.10
2.92
12.06
3.00
12.01
3.13
12.01
3.21
11.97
3.29
11.97
3.33
-9.8
-11
12.28
2.97
12.23
3.05
12.19
3.16
12.19
3.24
12.19
3.32
12.14
3.33
-9.5
-10
12.37
3.01
12.32
3.08
12.32
3.21
12.28
3.29
12.28
3.37
12.23
3.38
-8.5
-9.1
12.45
3.05
12.41
3.13
12.37
3.25
12.37
3.33
12.37
3.41
12.32
3.42
-7
-7.6
12.59
3.06
12.54
3.17
12.54
3.28
12.50
3.35
12.50
3.46
12.45
3.46
-5
-5.6
13.56
3.19
13.52
3.26
13.47
3.38
13.47
3.48
13.43
3.48
13.39
3.51
-3
-3.7
13.74
3.27
13.70
3.31
13.65
3.44
13.65
3.54
13.61
3.52
13.56
3.55
0
-0.7
14.01
3.36
13.96
3.34
13.92
3.48
13.92
3.58
13.87
3.58
13.87
3.58
3
2.2
15.47
3.56
15.29
3.56
15.25
3.66
15.20
3.73
15.20
3.77
15.16
3.80
5
4.1
19.24
4.30
18.46
4.25
18.17
4.23
17.46
4.09
16.75
4.05
15.38
3.87
7
6
19.55
4.33
18.82
4.13
18.17
4.02
17.46
3.92
16.75
3.88
15.38
3.74
9
7.9
19.55
4.12
18.82
3.93
18.17
3.90
17.46
3.85
16.75
3.78
15.38
3.65
11
9.8
19.55
3.92
18.82
3.77
18.17
3.77
17.46
3.72
16.75
3.67
15.38
3.51
13
11.8
19.55
3.73
18.82
3.66
18.17
3.66
17.46
3.65
16.75
3.59
15.38
3.45
15
13.7
19.55
3.61
18.82
3.58
18.17
3.56
17.46
3.51
16.75
3.49
15.38
3.32
120%
-13.7
-15
11.91
3.14
11.87
3.22
11.82
3.31
11.82
3.39
11.82
3.47
11.78
3.49
-11.8
-13
12.09
3.18
12.04
3.26
12.02
3.36
12.00
3.43
12.00
3.51
11.96
3.53
-9.8
-11
12.27
3.20
12.22
3.28
12.22
3.40
12.18
3.47
12.18
3.55
12.13
3.60
-9.5
-10
12.36
3.24
12.31
3.30
12.31
3.42
12.27
3.49
12.27
3.57
12.22
3.64
-8.5
-9.1
12.44
3.27
12.40
3.35
12.40
3.46
12.36
3.53
12.36
3.61
12.31
3.65
-7
-7.6
12.58
3.33
12.53
3.41
12.53
3.50
12.49
3.57
12.49
3.65
12.44
3.69
-5
-5.6
13.56
3.35
13.51
3.43
13.47
3.53
13.47
3.61
13.47
3.68
13.42
3.75
-3
-3.7
13.73
3.41
13.69
3.49
13.64
3.58
13.64
3.65
13.60
3.73
13.60
3.77
0
-0.7
14.00
3.46
13.96
3.54
13.91
3.61
13.91
3.68
13.91
3.76
13.87
3.80
3
2.2
15.29
3.67
15.29
3.76
15.24
3.79
15.20
3.87
15.20
3.94
14.22
3.76
5
4.1
19.24
4.11
18.09
4.07
16.80
4.00
16.13
3.92
15.51
3.88
14.22
3.65
7
6
19.38
4.08
18.09
3.90
16.80
3.80
16.13
3.73
15.51
3.71
14.22
3.56
9
7.9
19.38
3.90
18.09
3.72
16.80
3.68
16.13
3.61
15.51
3.60
14.22
3.45
11
9.8
19.38
3.78
18.09
3.64
16.80
3.56
16.13
3.50
15.51
3.47
14.22
3.32
13
11.8
19.38
3.68
18.09
3.55
16.80
3.46
16.13
3.45
15.51
3.41
14.22
3.25
15
13.7
19.38
3.60
18.09
3.45
16.80
3.36
16.13
3.32
15.51
3.29
14.22
3.13
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (comp outdoor fan motor) (kW)
Notes:
1. Shaded cells are tested under our standard condition.
2. Avoid running the outdoor unit when outdoor air temperature is below -15 degrees in heating mode.
3. The above table shows the average value of conditions may operate.
4. It is recommended to connect less than 130%.