V6R VRF 50Hz
Part 2 - Out
door Unit Engineering Da
ta
Mini Amazon III Series
79
Table 2-7.8: KMF-120 DVN4 heating capacity (continued)
Combination (%) (Capacity
index)
Outdoor temperature
(°C DB)
Indoor temperature(°C WB)
16.00
18.00
20.00
21.00
22.00
24.00
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
°C DB
°C WB
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
90%
-13.7
-15
11.78
3.84
11.73
3.88
11.73
3.92
11.69
3.94
11.64
3.78
10.67
3.40
-11.8
-13
11.96
3.85
11.91
3.89
11.91
3.93
11.87
3.89
11.64
3.70
10.67
3.34
-9.8
-11
12.13
3.85
12.13
3.90
12.09
3.93
12.09
3.81
11.64
3.63
10.67
3.28
-9.5
-10
12.22
3.86
12.22
3.90
12.18
3.94
12.13
3.78
11.64
3.60
10.67
3.24
-8.5
-9.1
12.31
3.86
12.27
3.90
12.27
3.93
12.13
3.74
11.64
3.57
10.67
3.22
-7
-7.6
12.44
3.87
12.44
3.85
12.40
3.87
12.13
3.69
11.64
3.51
10.67
3.17
-5
-5.6
13.42
3.87
13.38
3.68
12.62
3.71
12.13
3.57
11.64
3.40
10.67
3.08
-3
-3.7
13.60
3.88
13.56
3.52
12.62
3.53
12.13
3.44
11.64
3.30
10.67
3.00
0
-0.7
13.87
3.89
13.56
3.34
12.62
3.38
12.13
3.27
11.64
3.13
10.67
2.92
3
2.2
14.53
3.89
13.56
3.17
12.62
3.19
12.13
3.15
11.64
2.99
10.67
2.82
5
4.1
14.53
3.79
13.56
3.01
12.62
3.04
12.13
2.99
11.64
2.85
10.67
2.71
7
6
14.53
3.30
13.56
2.96
12.62
2.84
12.13
2.73
11.64
2.63
10.67
2.41
9
7.9
14.53
3.10
13.56
2.90
12.62
2.70
12.13
2.60
11.64
2.51
10.67
2.32
11
9.8
14.53
2.92
13.56
2.74
12.62
2.57
12.13
2.49
11.64
2.40
10.67
2.24
13
11.8
14.53
2.76
13.56
2.60
12.62
2.46
12.13
2.38
11.64
2.31
10.67
2.16
15
13.7
14.53
2.64
13.56
2.51
12.62
2.38
12.13
2.31
11.64
2.25
10.67
2.11
80%
-13.7
-15
11.73
3.86
11.69
3.90
11.20
3.57
10.76
3.40
10.36
3.24
9.47
2.93
-11.8
-13
11.91
3.87
11.87
3.82
11.20
3.49
10.76
3.33
10.36
3.18
9.47
2.88
-9.8
-11
12.09
3.87
12.04
3.75
11.20
3.43
10.76
3.27
10.36
3.12
9.47
2.82
-9.5
-10
12.18
3.87
12.04
3.71
11.20
3.39
10.76
3.24
10.36
3.09
9.47
2.79
-8.5
-9.1
12.27
3.88
12.04
3.68
11.20
3.37
10.76
3.21
10.36
3.06
9.47
2.77
-7
-7.6
12.40
3.88
12.04
3.62
11.20
3.32
10.76
3.17
10.36
3.02
9.47
2.74
-5
-5.6
12.93
3.81
12.04
3.51
11.20
3.22
10.76
3.07
10.36
2.94
9.47
2.66
-3
-3.7
12.93
3.94
12.04
3.38
11.20
3.08
10.76
2.96
10.36
2.83
9.47
2.58
0
-0.7
12.93
3.89
12.04
3.22
11.20
2.97
10.76
2.87
10.36
2.74
9.47
2.52
3
2.2
12.93
3.59
12.04
3.04
11.20
2.80
10.76
2.77
10.36
2.64
9.47
2.42
5
4.1
12.93
3.28
12.04
2.87
11.20
2.68
10.76
2.65
10.36
2.52
9.47
2.37
7
6
12.93
2.88
12.04
2.69
11.20
2.50
10.76
2.40
10.36
2.31
9.47
2.13
9
7.9
12.93
2.73
12.04
2.56
11.20
2.40
10.76
2.31
10.36
2.23
9.47
2.07
11
9.8
12.93
2.59
12.04
2.45
11.20
2.30
10.76
2.23
10.36
2.15
9.47
2.01
13
11.8
12.93
2.48
12.04
2.35
11.20
2.22
10.76
2.15
10.36
2.09
9.47
1.96
15
13.7
12.93
2.39
12.04
2.27
11.20
2.16
10.76
2.11
10.36
2.05
9.47
1.93
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (comp outdoor fan motor) (kW)
Notes:
1. Shaded cells are tested under our standard condition.
2. Avoid running the outdoor unit when outdoor air temperature is below -15 degrees in heating mode.
3. The above table shows the average value of conditions may operate.
4. It is recommended to connect less than 130%.