Mini Amazon III Series
76
Table 2-7.7: KMF-100 DVN4 heating capacity (continued)
Combination (%) (Capacity
index)
Outdoor temperature
(°C DB)
Indoor temperature(°C WB)
16.00
18.00
20.00
21.00
22.00
24.00
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
°C DB
°C WB
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
50%
-13.7
-15
5.20
1.80
4.86
1.71
4.51
1.64
4.31
1.57
4.14
1.52
3.80
1.40
-11.8
-13
5.20
1.73
4.86
1.64
4.51
1.57
4.31
1.52
4.14
1.46
3.80
1.34
-9.8
-11
5.20
1.68
4.86
1.58
4.51
1.50
4.31
1.45
4.14
1.40
3.80
1.29
-9.5
-10
5.20
1.62
4.86
1.52
4.51
1.44
4.31
1.39
4.14
1.34
3.80
1.22
-8.5
-9.1
5.20
1.55
4.86
1.46
4.51
1.38
4.31
1.33
4.14
1.28
3.80
1.15
-7
-7.6
5.20
1.49
4.86
1.40
4.51
1.33
4.31
1.28
4.14
1.23
3.80
1.10
-5
-5.6
5.20
1.44
4.86
1.35
4.51
1.26
4.31
1.23
4.14
1.18
3.80
1.05
-3
-3.7
5.20
1.39
4.86
1.30
4.51
1.21
4.31
1.18
4.14
1.13
3.80
1.01
0
-0.7
5.20
1.33
4.86
1.25
4.51
1.15
4.31
1.12
4.14
1.07
3.80
0.99
3
2.2
5.20
1.27
4.86
1.19
4.51
1.11
4.31
1.08
4.14
1.02
3.80
0.99
5
4.1
5.20
1.21
4.86
1.13
4.51
1.07
4.31
1.03
4.14
1.00
3.80
0.98
7
6
5.20
1.15
4.86
1.09
4.51
1.02
4.31
0.99
4.14
0.98
3.80
0.95
9
7.9
5.20
1.13
4.86
1.06
4.51
1.00
4.31
0.96
4.14
0.94
3.80
0.92
11
9.8
5.20
1.11
4.86
1.05
4.51
0.98
4.31
0.94
4.14
0.93
3.80
0.90
13
11.8
5.20
1.08
4.86
1.01
4.51
0.95
4.31
0.92
4.14
0.90
3.80
0.88
15
13.7
5.20
1.07
4.86
0.99
4.51
0.92
4.31
0.90
4.14
0.88
3.80
0.86
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (comp outdoor fan motor) (kW)
Notes:
1. Shaded cells are tested under our standard condition.
2. Avoid running the outdoor unit when outdoor air temperature is below -15 degrees in heating mode.
3. The above table shows the average value of conditions may operate.
4. It is recommended to connect less than 130%.