V6R VRF 50Hz
Part 2 - Out
door Unit Engineering Da
ta
Mini Amazon III Series
69
Table 2-7.6: KMF-80 DVN4 heating capacity (continued)
Combination (%)
(Capacity index)
Outdoor
temperature
(°C DB)
Indoor temperature(°C WB)
16.00
18.00
20.00
21.00
22.00
24.00
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
°C DB
°C WB
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
90%
-13.7
-15
6.06
2.21
6.03
2.23
6.03
2.25
6.01
2.26
5.99
2.17
5.49
1.95
-11.8
-13
6.15
2.21
6.13
2.23
6.13
2.26
6.10
2.23
5.99
2.13
5.49
1.92
-9.8
-11
6.24
2.21
6.24
2.24
6.22
2.26
6.22
2.19
5.99
2.09
5.49
1.88
-9.5
-10
6.29
2.22
6.29
2.24
6.26
2.26
6.24
2.17
5.99
2.07
5.49
1.86
-8.5
-9.1
6.33
2.22
6.31
2.24
6.31
2.26
6.24
2.15
5.99
2.05
5.49
1.85
-7
-7.6
6.40
2.22
6.40
2.21
6.38
2.22
6.24
2.12
5.99
2.02
5.49
1.82
-5
-5.6
6.90
2.22
6.88
2.11
6.49
2.13
6.24
2.05
5.99
1.95
5.49
1.77
-3
-3.7
6.99
2.23
6.97
2.02
6.49
2.03
6.24
1.97
5.99
1.89
5.49
1.72
0
-0.7
7.13
2.23
6.97
1.92
6.49
1.94
6.24
1.88
5.99
1.80
5.49
1.68
3
2.2
7.47
2.23
6.97
1.82
6.49
1.83
6.24
1.81
5.99
1.72
5.49
1.62
5
4.1
7.47
2.18
6.97
1.73
6.49
1.75
6.24
1.72
5.99
1.64
5.49
1.56
7
6
7.47
1.89
6.97
1.70
6.49
1.63
6.24
1.57
5.99
1.51
5.49
1.38
9
7.9
7.47
1.78
6.97
1.66
6.49
1.55
6.24
1.50
5.99
1.44
5.49
1.33
11
9.8
7.47
1.67
6.97
1.57
6.49
1.48
6.24
1.43
5.99
1.38
5.49
1.28
13
11.8
7.47
1.58
6.97
1.50
6.49
1.41
6.24
1.37
5.99
1.33
5.49
1.24
15
13.7
7.47
1.52
6.97
1.44
6.49
1.36
6.24
1.33
5.99
1.29
5.49
1.21
80%
-13.7
-15
6.03
2.22
6.01
2.24
5.76
2.05
5.53
1.95
5.33
1.86
4.87
1.68
-11.8
-13
6.13
2.22
6.10
2.20
5.76
2.01
5.53
1.91
5.33
1.83
4.87
1.65
-9.8
-11
6.22
2.22
6.19
2.15
5.76
1.97
5.53
1.88
5.33
1.79
4.87
1.62
-9.5
-10
6.26
2.22
6.19
2.13
5.76
1.95
5.53
1.86
5.33
1.77
4.87
1.60
-8.5
-9.1
6.31
2.23
6.19
2.11
5.76
1.93
5.53
1.84
5.33
1.76
4.87
1.59
-7
-7.6
6.38
2.23
6.19
2.08
5.76
1.91
5.53
1.82
5.33
1.73
4.87
1.57
-5
-5.6
6.65
2.19
6.19
2.01
5.76
1.85
5.53
1.76
5.33
1.69
4.87
1.53
-3
-3.7
6.65
2.26
6.19
1.94
5.76
1.77
5.53
1.70
5.33
1.62
4.87
1.48
0
-0.7
6.65
2.23
6.19
1.85
5.76
1.71
5.53
1.65
5.33
1.58
4.87
1.45
3
2.2
6.65
2.06
6.19
1.75
5.76
1.61
5.53
1.59
5.33
1.52
4.87
1.39
5
4.1
6.65
1.89
6.19
1.65
5.76
1.54
5.53
1.52
5.33
1.44
4.87
1.36
7
6
6.65
1.65
6.19
1.54
5.76
1.44
5.53
1.38
5.33
1.33
4.87
1.22
9
7.9
6.65
1.57
6.19
1.47
5.76
1.38
5.53
1.33
5.33
1.28
4.87
1.19
11
9.8
6.65
1.49
6.19
1.40
5.76
1.32
5.53
1.28
5.33
1.24
4.87
1.16
13
11.8
6.65
1.42
6.19
1.35
5.76
1.27
5.53
1.24
5.33
1.20
4.87
1.13
15
13.7
6.65
1.37
6.19
1.30
5.76
1.24
5.53
1.21
5.33
1.17
4.87
1.11
Abbreviations:
CR: Combination ratio
TC: Total capacity (kW)
PI: Power input (comp outdoor fan motor) (kW)
Notes:
1. Shaded cells are tested under our standard condition.
2. Avoid running the outdoor unit when outdoor air temperature is below -15 degrees in heating mode.
3. The above table shows the average value of conditions may operate.
4. It is recommended to connect less than 130%.