DS200 Installation Guide
DS200 Installation Guide
DS200 Installation Guide
DS200 Installation Guide
V003. 25.06.2002
B-17
2- Connect the cables of the accessories to the connectors on the DS200 CPUKON. In order
to do this, extend the cables through the cable hole that is in the lower front rack and
attach them to the corresponding connectors on the DS200 CPUKON card. Then take the
free end of the cable out of the rack by extending it along underneath the rack through
the corresponding path within the cable channel that has been fixed on the back cover.
3- Install DS200 CPUKON card together with DS200 CPU-FC cable. First, attach the DS200
CPU-FC cable to the connector on the DS200 CPUKON card. Then, insert the DS200
CPUKON card so as its back corners fit the channel of the plastic card slot. Afterwards,
extend the free end of the DS200 CPU-FC cable along underneath the UTIL200 connector
on the backplane. As for the final step, when the card is completely placed, fix the DS200
CPUKON card by the fixing latches on the plastic card holder. See the figure below for
the correct usage of the plastic fixing latches.
Figure – 10
4- In order to install the CPU200 module, place the back corners of the module into the
channel of the plastic card slot and push it towards the rack. Before you set the module
completely, connect the DS200 CPU-FC cable to CPU200. Then, push the CPU200 module
inside, so as it tightly fits on its corresponding connector on the BPL200-Backplane.
When the module has been completely set, fix it by using fixing latches on the front cover
of the card. (See The Technical Reference GuideFigure – 24). See Figure – 10 for the
correct usage of the plastic fixing latches.
In case it is necessary to take CPU200 out of the rack, press the card fixing latches on the
front cover of CPU200 toward the tag on the holder and then pull the module cautiously until
DS200 CPU-FC appears. As for the final step, detach DS200 CPU-FC from CPU200 and then
take it out of the rack.
In case it is necessary to take DS200 CPUKON out of the rack, press the card fixing latches
on the front cover of the card toward the tag on the holder and then pull the module
cautiously until DS200 CPU-FC appears. Afterwards, detach DS200 CPU-FC from DS200
CPUKON and take it out of the rack.
If a redundant CPU200 is needed in the system, then install that card in the special slot at the
right-hand side of CPU200, which is reserved for it by following the same installation steps
as for CPU200. Its connection to DS200 CPUKON card is provided by DS200 CPU-FC.
!
DO NOT EVER REMOVE THE CPU200 CARD DURING THE OPERATION
OF THE EXCHANGE.
I.4.A.1. THE LAN ADAPTOR CARD: