The four-rack cabinet is used, if a system has four racks. In this case, since the entire racks
will fit into that cabinet, single-cabinet installation will suffice. The rack that will fit into the
uppermost rack slot of the cabinet will be of the main rack structure, too, like the first rack.
In two-cabinet systems, the first racks (lowermost) will be main rack and the others will be
auxiliary racks. However, there is CPU200 card only in a single cabinet’s main rack.
Likewise, there is DS200 CPUKON card in only a single main rack.
The first and the fourth racks are of the main rack structure and the connection between
these two racks is provided with some additional cards and cables. The list of those cards
and cables are below:
1) CC Extra card
2) C Master card
3) C Slave card
4) CC Enable card
5) Two BPL200-FC
6) Five PCM carrier cable
7) BPLSPS-FCX cable
In order to facilitate the connection of the two cabinets, you need to remove the SPS248
power units, UTIL200, DS200 CPUKON and CPU200 cards (redundant CPU200, too, if there is
any.)
I.2.C.1. CONNECTIONS IN THE MAIN RACK, TO WHICH THE
CPU200 CARD HAS BEEN ATTACHED:
I.2.C.1.1. ATTACHING THE CC EXTRA CARD ONTO THE CPU200 CARD:
Attach the card to the 20-pin connector with the code CON402, in a manner as it coincides
with the lower back corner of the CPU200 card that has been indicated with white lines,
through the female connector that is on the CC Extra card.