DS200 Installation Guide
DS200 Installation Guide
DS200 Installation Guide
DS200 Installation Guide
V003. 25.06.2002
B-10
Figure – 6
If there will be a redundant CPU200 card in the system, then you should attach another CC
Extra card onto that redundant CPU200 card, too.
I.2.C.1.2. INTEGRATION OF THE C MASTER CARD TO THE MAIN RACK:
The C Master card must be attached to the main rack on which there is CPU200. Structure of
this card is suitable for attaching it to the plastic card slots of DS200 and its size is the same
as that of the CPU200 card. However, there is no 64-pin male connector at the back of the
card for the backplane connection. Instead, it is connected by a BPL200-FC to the inter-rack
connector that is at the lower section on the BPL200 backplane of the main rack, at the same
level with the CPU200.
If, on the other hand, there will not be a redundant CPU200 card in the DS200 system, then
the C Master card is attached to the slot that is reserved for the redundant CPU200 card.
Connect the cables before completely fixing the card in the slot.
The procedure for this:
1) Connect one end of the BPL200-FC to the inter-rack connector that is at the lower edge
of the BPL200-MAIN backplane of the main rack.
2) Connect the other end of the BPL200-FC to the similar connector that is on the C Master
card.
3) Connect the PCM carrier cables to the five RJ45 connectors that are on the C Master
card. The connection order of those cables is essentially important because those cables
will be connected to the second rack in the same order.