KaDeck
Assembly instructions
EN
Assembly instructions
4
SAP 1538177 01/22
1
Overview
1
2
3
4
5
6
7
KaDeck at a glance (example shows air discharge on two sides)
1
Design panel
2
Filter
3
Securing panel
4
Condensate tray
5
Suspension bracket
6
Condensate pump
7
Electrical junction box
2
Safety
This section provides an overview of all important safety aspects for protecting personnel. In ad-
dition to the safety notes in this and the more detailed instruction in accordance with the QR
Code, the occupational health and safety and environmental protection regulations applicable to
the unit's field of application, as well as the notes in accordance with EN60335-1, must be ob-
served.
2.1
Correct use
The units are only intended to be used for heating and cooling air in frost-free and dry rooms.
Within the room, the unit needs to be connected to the building's heating/cooling/ventilation
system and to the building's waste water and power network. The operating limits and limits of
use described in
must be observed.
IMPORTANT NOTE!
Only use the unique after completion of the complete building and system. Site
heating is not deemed to be correct and proper use.
Intended use of the unit also includes adherence to these instructions.
Any use beyond or other than the stated intended use is considered as misuse.
Any change to the unit or use of non-original spare parts will cause the expiry of the warranty
and the manufacturer’s liability.
2.2
Limits of operation and use
Limits of operation
Min./max. water temperature
°C
4-80
Min./max. air intake temper-
ature
°C
6-40
Min./max. air humidity
%
20-60
Min. operating pressure
bar/kPa
-
Max. operating pressure
bar/kPa
16/1600
Min./max. glycol percentage
%
0-50
Operating voltage
230 V/ 50/60 Hz
Power/Current consumption
On the type plate
IMPORTANT NOTE!
Danger of frost in cooling mode!
There is a risk of the heat exchanger freezing when used in unheated rooms.
Protect the unit from frost.
IMPORTANT NOTE!
Warning of misuse!
In the event of misuse, as itemised below, there is a danger of limited or failing
operation of the unit. Ensure that the airflow can circulate freely.
Never operate the unit in humid areas, such as swimming pools, wet areas
etc.
Never operate the unit in rooms with an explosive atmosphere.
Never operate the unit in aggressive or corrosive atmospheres (e.g. sea air).
Never operate the unit above electrical equipment (such as switch cabinets,
computers or other electrical units, or contacts that are not drip-proof).
Never use the unit as a construction site heater.
2.3
Risk from electrocution!
DANGER!
Risk of fatal injury from electrocution!
Contact with live parts will lead to fatal injury from electrocution. Damage to the
insulation or individual components can lead to a fatal injury.
Only permit qualified electricians to work on the electrical system.
Immediately disconnect the system from the power supply and repair it in
the event of damage to the insulation.
Keep live parts away from moisture. This can cause a short circuit.
Properly earth the unit.
Assembly, installation and operating
instructions:
Kampmann GmbH & Co. KG
Friedrich-Ebert-Str. 128-130
49811 Lingen (Ems)
T: +49591/7108 0
www.kampmann.de
Содержание 32611641111100
Страница 20: ...KaDeck 20 2 4 VDE DIN EN VDI 6022 B C 2 5 3 3 1 Kampmann 2 4 4 1 4 2 2 2 2 3 4 3 1 M8 2 M8 3 4 5 90 6 23...
Страница 21: ...KaDeck 21 4 4 2 2 2 4 2 4 1 2 2 2 3 4 5 6 5 DIP...
Страница 22: ...KaDeck 22 6 6 1 6 2...
Страница 23: ...23 1 31 1 24 4 7 7 7 7 790 620 195 195 2 3 4 5 6...
Страница 24: ...24 7 8...