background image

2 3

5 6

8 9

11 12

7

4

1

10

30

002

sn

1 7

Settings

 –

 

Min. Switch Time  (1 – 600 sec)

5

Enter Min.SwitchTime

2 3

5 6

8 9

11 12

7

4

1

10

30

Apply

▲ +

▼ -

002

Save

changes

sec

Cancel

Okay

Back

This is the section in which the value of step sub-period (min) is entered (sec). The value is setup 

to the required step by using up and down keys starting from the digit where the blue line is. Then, 

left key is pressed and the blue line moves next to left digit. All values are entered in the same 

way by using the up and down keys.

Press “Apply” key inorder to take the step sub-period (min) time into memory. “Save changes” 

message will appear on the screen. When “Okay” key is pressed, the value is taken into memory.

Period of activating line is subjected to a function with the % value obtained from the ratio of 

energies. It represents the minimum value of both step activating and de-activating time which can 

be changed by the device.

Step sub-period is not taken into

account during fast mode.

2 3

5 6

8 9

11 12

7

4

1

10

30

020

sn

1 7

Settings

 –

 

Switch Off

 

time   (1 – 600 sec)

4

Enter Step Switch Off Time

2 3

5 6

8 9

11 12

7

4

1

10

30

Apply

▲ +

▼ -

020

Save

changes

sec

Cancel

Okay

Back

This is the section in which the value of switch off time is entered (sec).  The value is setup to the 

required step by using up and down keys starting from the digit where the blue line is.  Then, left 

key is pressed and the blue line moves next to left digit. All values are entered in the same way by 

using the up and down keys.

Press “Apply” key in order to take the switch off time into memory. “Save changes” message will 

appear on the screen. When “Okay” key is pressed, the value is taken into memory.

Period of activating line is subjected to a function with the % value obtained from the ratio of 

energies. In case % value is getting close to the capactive penalty line value, the time is reduced 

automatically by the device. If necessasy, compensation speeds up; and if not, it slows down by 

means of dynamic control of switch off time, and continously do not make fast moves 

unnecessarily. 

P.S.1: Switch off  time counts only for capacitor activated newly. If necessary and a close solution 

is found in another step, device deactivates the other option on time and the compensation is not 

delayed.

If it' s not required the device to respond so quickly, holding period between the steps can be 

extended to delay releasing process by increasing the value of ΔT off switching time described in 

the next 

        chapter.

P.S.2: In case fast operating mode

is selected, switch off time of the 

device is 200 msec.

It' s independent from switch off

time which is set-up.

P.S.3: In case of selecting the 

switch off time less than min.step 

time, device accepts the switch off 

time as constant time value.

1 7 10 2

Other Relays :

 

They proceed the step de-activating transaction with constant time adjusted. If the 

time is not over, they will wait for the deadline. This causes delays in the compensation.
VARkombi-12-PC-TFT-OG :

 

It collects the energies (ind., cap., active) consumed. Step activating 

and de-activating periods are decreased or increased automatically by the device according to the 

consumed enerygy.

P.S.: The energies consumed in VARkombi-12-PC-TFT-OG and the % values are calculated 

separately for each phase. Therefore, step activating and de-activating periods of each phase can 

vary. For instance, while the step de-activating time for R-phase down to 2 seconds, the one for 

S-phase can be 7 sec. VARkombi-12-PC-TFT-OG analyze the system phase by phase and set-

up the compensation rate for each phase seperately.

The most simple explanation

regarding the ratio of energy

of step de-activating period has

been given below. 

In fact the function consists of 

much more complicated and an

array of fuzzy logic. Level sub-

period (min) determines the

lowest time value of step de-activating

time which can be reduced by the device.

This parameter can be specified by the user.

% cap.

Switch Off time

0

Min. Step Time

% cap.penalty line value

t(sec)

13

200 msec

Fast Mode

Normal Mode

Enter Step Switch Off Time

Enter Min.Switch Time

Содержание VARkombi-12-PC-TFT-OG

Страница 1: ...dislik Elektronik Tic ve San Ltd ti Reactive Power Control Relay Industrial Facilities Markets Oil Stations Schools Workshops Hotels 12 Step VARkombi 12 PC TFT OG Connection type selective VARkombi 12...

Страница 2: ...7 8 Current Transformer Primary Value 1 7 9 Number of Steps 1 7 10 Advanced Set up Menu 1 7 10 1 T on Transition Delay Time 1 7 10 2 T off Transition Delay Time 1 7 10 3 Current Flow Direction Detecti...

Страница 3: ...ver Temperature 1 7 10 6 2 4 Voltage THD Setting 1 7 10 6 2 5 Voltage HD Setting 1 7 10 6 2 6 Current THD Setting 1 7 10 6 2 7 Current HD Setting 1 7 10 6 3 Fan Settings 1 7 10 6 3 1 Fan Temperature V...

Страница 4: ...the device for different purposes other than compensation system 6 Fix the device tightly on the control panel with the apparatus given on the device without hanging around 7 Do not interfere to the...

Страница 5: ...king compensation for the generator according to the second Cos 2 set up Displaying many guiding screens operating system is used in the micro processor Computer communicated RS485 MODBUS RTU Password...

Страница 6: ...g to the specified current value The outputs of the steps are not needed to be made in any order However the first 6 steps can consist of triple phase capacitor groups It is recomended to connect sing...

Страница 7: ...er the other according to the priority Meanwhile the phase in which the alarm is given displayed on the screen Arrow keys can move between the alarms In case Select key is pressed during on any alarm...

Страница 8: ...e checked again in case any power of the steps and their connections are not intenalized for a long time 5 Step Learning of step powers For more info When all the steps are internalized the main scree...

Страница 9: ...umptions Instant consumption values of each phase and their scaled representation the normal under and over compensation of the phases their inductive capacitive characterized loads and whether the sy...

Страница 10: ...rol Otherwise the device remains in manual control continuously 1 2 3 4 5 6 7 8 9 11 10 12 30 Menu Cos PF Steps 0 R S T 0 ind cap ind cap ind cap S T Q 1 763K P 21 44K PF 0 991 0 155K 14 66K 0 999 1 4...

Страница 11: ...tep with red frame among the step boxes is displayed on the left side of the screen while moving with directon keys The information regarding the runtime of all steps number of switching phase or phas...

Страница 12: ...ave Changes appears on the screen the data are kept in the memory by pressing Okay key Settings This is the section in which you can find all set up regarding the device Password is entered After comm...

Страница 13: ...r DYN 5 NOTE The current transformer ratio must be entered in the section from the menu 1 7 8 select exit 1 7 Measurement types MV LV ratio Transformer Type 2 3 5 6 8 9 11 12 7 4 1 10 30 1 1 Enter MV...

Страница 14: ...1 10 30 Connection MEDIUM VOLTAGE LOW VOLTAGE Voltage become isolated The value of the voltage transformer must be entered NOTE The current transformer ratio must be entered in the section from the m...

Страница 15: ...or the deadline This causes delays in the compensation VARkombi 12 PC TFT OG It collects the energies ind cap active consumed Step activating and de activating periods are decreased or increased autom...

Страница 16: ...lows down by means of dynamic control of switch off time and continously do not make fast moves unnecessarily P S 1 Switch off time counts only for capacitor activated newly If necessary and a close s...

Страница 17: ...ge will appear on the screen When Okay key is pressed the value is taken into memory Enter cap penalty limit 2 3 5 6 8 9 11 12 7 4 1 10 30 Apply 10 Enter cap penalty limit 2 3 5 6 8 9 11 12 7 4 1 10 3...

Страница 18: ...s are entered in the same way by using the up and down keys Press Apply key inorder to take T off switching time into memory Save changes message will appear on the screen When Okay key is pressed the...

Страница 19: ...ation in some plants especially the plants in which the loads are changing very quickly The required status for function is selected by using the up and down keys Press Apply key inorder to take this...

Страница 20: ...2 3 5 6 8 9 11 12 7 4 1 10 14 30 Exit 3 phase Select R S T 1 Step 1 phase 0 000 KVAr 0 000 KVAr 0 000 KVAr 0 000 KVAr 2 3 5 6 8 9 11 12 7 4 1 10 30 3 phase R S T 1 Step 1 phase 0 000 KVAr 0 000 KVAr 0...

Страница 21: ...00 K Step Change 2 3 4 5 6 8 9 10 11 12 16 17 14 15 1 7 13 2 3 5 6 8 9 11 12 7 4 1 10 30 Exit Load New value Old value Old value R S T 0 000 K 0 000 K 0 000 K 0 000 K Step Change 2 3 4 5 6 8 9 10 11 1...

Страница 22: ...under compensation in any phase during the activation of alert device warns the user In this case Review the capacitor power distribution in the steps especially in the phase where the alert is given...

Страница 23: ...s may blowed out The fuses in the power line of capacitors may blowed out Removing the failure steps internalized zero should be internalized again 1 7 10 6 1 General Alarms Over Temperature enable 2...

Страница 24: ...digit All values are entered in the same way by using up and downkeys Select key is pressed to take them into the memory Save changes message will appear on the screen Pressing Okay key the value is...

Страница 25: ...essing Okay key the value is taken into the memory 5 005 Voltage HD Alarm Setting HDV Save Changes In case harmonic protection is activated in the step protection function Chapter 1710643 all steps ar...

Страница 26: ...0 30 Apply disable Fan Output 1 7 10 6 4 Setting Advanced Setting Menu Alarm Protection Step Protection Function De activation of the capacitors is recommended to protect them against temperature volt...

Страница 27: ...30 Apply Enable User Password Status 2 3 5 6 8 9 11 12 7 4 1 10 30 Exit Password active passive Password change 1 7 9 7 2 PASSWORD Enter old password 0 2 3 5 6 8 9 11 12 7 4 1 10 30 Exit Password acti...

Страница 28: ...ssword should be entered to write data This is the section in which the password is entered The value is setup to the required value by using the up and down key starting from the digit where the blue...

Страница 29: ...ing Okay key the value is taken into the memory Device No 001 255 The value is setup to the required value by using the up and down key starting from the digit where the blue line is Then left key is...

Страница 30: ...ting Values THD Current 30 Alarm Setting Values HD Current 30 Fan Settings Fan Temperature Value 50 C Fan Settings Fan Output disable Level Protection Function Temperature Protection disable Level Pro...

Страница 31: ...Class IP 20 Terminal Protection Class IP 00 Environment Temperature 5 C 50 C Humudity 15 95 without condensation Device Standart EN 55011 2007 A2 2007 EN 61326 2006 EN 61000 3 2 2006 EN 61000 3 3 1995...

Страница 32: ...A CALCULATION CHART ACCORDING TO CAPACITOR CONNECTION FORMAT Capacitor Powers 3 Phase Connection Phase Neutral Connection Phase Neutral bridged Connection Phase Phase Connection Phase Phase bridged Co...

Отзывы: