Factory Defaults
This is the section which is used to restore factory default values to the
device.
Factory Default Values :
Target TanΦ(cosΦ)
: % 0
Switch on (Decharge) Time
: 20 sec
Switch off Time
: 15 sec
Switch min. Time
: 10 sec
Inductive Penalty Limit (%)
: % 15
Capacitive Penalty Limit (%)
: % 10
Current Transformer (Primary) Value
:
5
/ 5 A
Number of steps
: 12
ΔT on Transition(Delay) Time
: 0 sec
ΔT off Transition(Delay) Time
: 0 sec
Continuous Current Flow Direction Detection
: enable
Fast Step Mode
: enable
Connection Type
: WYE
Continuous Step Power Detection
: enable
Constant Step Function
: disable
Step Synch. Time Sharing
: disable
Phase Alarms – Over Voltage
: enable
Phase Alarms – Under Voltage
: enable
Phase Alarms – Over Current
: enable
Phase Alarms – Over Compensation
: enable
Phase Alarms – Under Compensation
: enable
Phase Alarms – No Phase
: enable
Phase Alarms – THD on Voltage
: enable
Phase Alarms – HD on Voltage
: enable
Phase Alarms – THD on Current
: enable
Phase Alarms – HD on Current
: enable
General Alarms – 1. connector failure
: enable
General Alarms – 2. connector failure
: enable
General Alarms – Total Over Compensation
: enable
General Alarms – Total Under Compensation
: enable
General Alarms – System Failure
: enable
General Alarms – Over Temperature
: enable
General Alarms – Voltage Connection Failure
: enable
General Alarms – Step Change
: enable
General Alarms – Step Zero
: enable
General Alarms – Modbus Security Failure
: enable
Alarm Setting Values – Over Voltage
: 250V
Alarm Setting Values – Under Voltage
: 180V
Alarm Setting Values – Over Temperature
: 70 °C
Alarm Setting Values – THD Voltage
: % 10
Alarm Setting Values – HD Voltage
: % 10
Alarm Setting Values – THD Current
: % 30
Alarm Setting Values – HD Current
: % 30
Fan Settings – Fan Temperature Value
: 50 °C
Fan Settings – Fan Output
: disable
Level Protection Function–Temperature Protection: disable
Level Protection Function – Voltage Protection
: disable
Level Protection Function – Harmonic Protection : disable
Password Procedure – Password Settings
: enable
Password Procedure – Default Password
: 0000 (refer to PS1)
MODBUS RTU Setup – Data Write Protection
: disable
MODBUS RTU Setup – Data Read Protection
: disable
MODBUS RTU Setup – Data Write Password
: 0000 (refer to PS2)
MODBUS RTU Setup – Data Read Password
: 0000 (refer to PS2)
MODBUS Port Setup – Baud Rate
: 9600
MODBUS Port Setup – Stop Bits
: 1
MODBUS Port Setup – Parity
: No
MODBUS Port Setup – Device No
: 1
Select
▼
Exit
▲
1 8
SETUP
►
Factory Defaults
Power
Energy
Counter Index
Settings
30
Yes
Cancel
Device
will return
factory settings
30
Yes
Cancel
30
Install the device
to the Factory
Settings
Device
will reset ?
1
2 3 4 5 6 7 8 9 10 11 12
30
Factory defaults
of the device are loading
In case of restoring factory settings, all the changes that the user made, except password, will be cancelled.
PS 1 :
User password is defined as “0000” at first. However, after password is changed, password will not change even if
returned to the factory settings. The last password that the user entered is valid.
PS 2 :
It is different than the user password of the device. However it can be entered into the device manually, it can not
be changed by remote access. In case of restoring factory settings, “0000” is appointed to modbus password.
PS 3 :
In case of restoring factory settings, the current directions, capacitor powers, energies and counter indexes that
the device internalized before, are reset.