General

Electricity networks are gradually overloaded as a result of increasing use and demand of 

emerging technologies In all sectors. While the compensation becomes a nightmare for the  

companies having unstable load, even the companies having stable load in the past  have now 

difficulties to provide reactive compensation. Therefore, the period of reactive power relays 

measured by single-phase will be over in the close future. KAEL Elektronik has incorporated a 

brand-new device to the electricity sector having much more steps, quite good equipped in terms 

of function means and software with improved running algorithms, by combining the achievements 

and experiences coming along with VARkombi-12-PC-TFT-OG regarding the reactive power 

compensation.   

Facilities are provided to the users with many graphics and animation by using large 3.2 " color 

LCD screen on the device. Moreover, the microprocessor in the device is running very fast and an 

operating system is used. This provides to reach all transactions running simultaneously.

In case the 

blue led

 on the lower left corner of the front panel of the device flashes, this 

means it is close to the value of penalty % and authorized persons should be informed as 

soon as possible. This is also useful in terms of taking the attention of the end-user in 

case of penalty who does not know this functional issue. 

■  The connections of the device should be made while the system is energy-free.

■  VARkombi-12-PC-TFT-OG should be connected as shown in the connection diagram.

■  Three phase and neutral connections should be made to the voltage input. Phase should not 

be given instead of neutral. Otherwise the device can be damaged.

■  Current connections should be made as to match the same phase with the same current 

transformer. Scheme should be followed.

■  The value of the selected current transformers should not be under the real load values but  

should be X/5 amper.  It is also advised to choose 0.5 class.

■  Connect the “C1, C2, C3” common phase inputs to the same phase with FF type fuses 
seperately. Select the fuses to be used according to the specified current value.

 

■  The outputs of the steps are not needed to be made in any order. However, the first 6 steps 

can consist of triple-phase capacitor groups. It is recomended to connect single-phase 

capacitors to the second and third 6 steps and, to connect capacitors or reactors to the third 6 

steps in terms of accepting the statements in this manual. 

■  Make the connections to the generator if it is used.

■  Make RS485 connection. (Not applicable in VARkombi-12-TFT-OG)

■  Do not energize the device without ensuring the connections checked by measurement 

instruments.

Making the Connections

1 2 3

4

5 6

7

8

9

11

10

12

30

Temperature (ºC)

1. 

step

Capacitor step not 
activated

Capacitor step 
activated (

blue

)

1

R

S

T

Step Indicator

The powers and the phases they are belonging to are 
not yet informed

A step indicator made by symbols that can be easily realized by the user, is located on the upper 

part of the screen of VARkombi-12-PC-TFT-OG. No matter which part of the user in, this panel is 

always located on the top of the screen. Step numbers, the phase or the phases they are 

connected, whether these are informed or not, whether they are capacitors or reactors, whether 

the steps and the generators are activated or not and control panel temperature value can all be 

observed on this panel at the same time. 

LCD screen is used in VARkombi-12-PC-TFT-OG to provide it to be more easier in use 

and be intelligible. In case the keys are not pressed for a long time, the device switch to the 

screen saver mode to extend the life of the display, and only the step indicator shown on the the 

top scrolls down step by step from the top to the bottom of the screen. Thus, the condition of the 

steps can be continued to be monitored. In case of pressing on any key, the main screen image 

appears again. 

Compensation normal

Fast mode activated

The following symbols can be seen on this part of the 
display.

Manual control

3

!

H

F

I V

I V

I V

I V

Measurement:

 Current from 

medium voltage side – voltage from 
low voltage side(non-insulated)

I V

Measurement:

 Current from 

medium voltage side – voltage from 
medium voltage side

Measurement:

 Current from low 

voltage side – voltage from low 
voltage side (insulated)

Measurement:

 Current from low 

voltage side – voltage from low 
voltage side (non-insulated)

Содержание VARkombi-12-PC-TFT-OG

Страница 1: ...dislik Elektronik Tic ve San Ltd ti Reactive Power Control Relay Industrial Facilities Markets Oil Stations Schools Workshops Hotels 12 Step VARkombi 12 PC TFT OG Connection type selective VARkombi 12...

Страница 2: ...7 8 Current Transformer Primary Value 1 7 9 Number of Steps 1 7 10 Advanced Set up Menu 1 7 10 1 T on Transition Delay Time 1 7 10 2 T off Transition Delay Time 1 7 10 3 Current Flow Direction Detecti...

Страница 3: ...ver Temperature 1 7 10 6 2 4 Voltage THD Setting 1 7 10 6 2 5 Voltage HD Setting 1 7 10 6 2 6 Current THD Setting 1 7 10 6 2 7 Current HD Setting 1 7 10 6 3 Fan Settings 1 7 10 6 3 1 Fan Temperature V...

Страница 4: ...the device for different purposes other than compensation system 6 Fix the device tightly on the control panel with the apparatus given on the device without hanging around 7 Do not interfere to the...

Страница 5: ...king compensation for the generator according to the second Cos 2 set up Displaying many guiding screens operating system is used in the micro processor Computer communicated RS485 MODBUS RTU Password...

Страница 6: ...g to the specified current value The outputs of the steps are not needed to be made in any order However the first 6 steps can consist of triple phase capacitor groups It is recomended to connect sing...

Страница 7: ...er the other according to the priority Meanwhile the phase in which the alarm is given displayed on the screen Arrow keys can move between the alarms In case Select key is pressed during on any alarm...

Страница 8: ...e checked again in case any power of the steps and their connections are not intenalized for a long time 5 Step Learning of step powers For more info When all the steps are internalized the main scree...

Страница 9: ...umptions Instant consumption values of each phase and their scaled representation the normal under and over compensation of the phases their inductive capacitive characterized loads and whether the sy...

Страница 10: ...rol Otherwise the device remains in manual control continuously 1 2 3 4 5 6 7 8 9 11 10 12 30 Menu Cos PF Steps 0 R S T 0 ind cap ind cap ind cap S T Q 1 763K P 21 44K PF 0 991 0 155K 14 66K 0 999 1 4...

Страница 11: ...tep with red frame among the step boxes is displayed on the left side of the screen while moving with directon keys The information regarding the runtime of all steps number of switching phase or phas...

Страница 12: ...ave Changes appears on the screen the data are kept in the memory by pressing Okay key Settings This is the section in which you can find all set up regarding the device Password is entered After comm...

Страница 13: ...r DYN 5 NOTE The current transformer ratio must be entered in the section from the menu 1 7 8 select exit 1 7 Measurement types MV LV ratio Transformer Type 2 3 5 6 8 9 11 12 7 4 1 10 30 1 1 Enter MV...

Страница 14: ...1 10 30 Connection MEDIUM VOLTAGE LOW VOLTAGE Voltage become isolated The value of the voltage transformer must be entered NOTE The current transformer ratio must be entered in the section from the m...

Страница 15: ...or the deadline This causes delays in the compensation VARkombi 12 PC TFT OG It collects the energies ind cap active consumed Step activating and de activating periods are decreased or increased autom...

Страница 16: ...lows down by means of dynamic control of switch off time and continously do not make fast moves unnecessarily P S 1 Switch off time counts only for capacitor activated newly If necessary and a close s...

Страница 17: ...ge will appear on the screen When Okay key is pressed the value is taken into memory Enter cap penalty limit 2 3 5 6 8 9 11 12 7 4 1 10 30 Apply 10 Enter cap penalty limit 2 3 5 6 8 9 11 12 7 4 1 10 3...

Страница 18: ...s are entered in the same way by using the up and down keys Press Apply key inorder to take T off switching time into memory Save changes message will appear on the screen When Okay key is pressed the...

Страница 19: ...ation in some plants especially the plants in which the loads are changing very quickly The required status for function is selected by using the up and down keys Press Apply key inorder to take this...

Страница 20: ...2 3 5 6 8 9 11 12 7 4 1 10 14 30 Exit 3 phase Select R S T 1 Step 1 phase 0 000 KVAr 0 000 KVAr 0 000 KVAr 0 000 KVAr 2 3 5 6 8 9 11 12 7 4 1 10 30 3 phase R S T 1 Step 1 phase 0 000 KVAr 0 000 KVAr 0...

Страница 21: ...00 K Step Change 2 3 4 5 6 8 9 10 11 12 16 17 14 15 1 7 13 2 3 5 6 8 9 11 12 7 4 1 10 30 Exit Load New value Old value Old value R S T 0 000 K 0 000 K 0 000 K 0 000 K Step Change 2 3 4 5 6 8 9 10 11 1...

Страница 22: ...under compensation in any phase during the activation of alert device warns the user In this case Review the capacitor power distribution in the steps especially in the phase where the alert is given...

Страница 23: ...s may blowed out The fuses in the power line of capacitors may blowed out Removing the failure steps internalized zero should be internalized again 1 7 10 6 1 General Alarms Over Temperature enable 2...

Страница 24: ...digit All values are entered in the same way by using up and downkeys Select key is pressed to take them into the memory Save changes message will appear on the screen Pressing Okay key the value is...

Страница 25: ...essing Okay key the value is taken into the memory 5 005 Voltage HD Alarm Setting HDV Save Changes In case harmonic protection is activated in the step protection function Chapter 1710643 all steps ar...

Страница 26: ...0 30 Apply disable Fan Output 1 7 10 6 4 Setting Advanced Setting Menu Alarm Protection Step Protection Function De activation of the capacitors is recommended to protect them against temperature volt...

Страница 27: ...30 Apply Enable User Password Status 2 3 5 6 8 9 11 12 7 4 1 10 30 Exit Password active passive Password change 1 7 9 7 2 PASSWORD Enter old password 0 2 3 5 6 8 9 11 12 7 4 1 10 30 Exit Password acti...

Страница 28: ...ssword should be entered to write data This is the section in which the password is entered The value is setup to the required value by using the up and down key starting from the digit where the blue...

Страница 29: ...ing Okay key the value is taken into the memory Device No 001 255 The value is setup to the required value by using the up and down key starting from the digit where the blue line is Then left key is...

Страница 30: ...ting Values THD Current 30 Alarm Setting Values HD Current 30 Fan Settings Fan Temperature Value 50 C Fan Settings Fan Output disable Level Protection Function Temperature Protection disable Level Pro...

Страница 31: ...Class IP 20 Terminal Protection Class IP 00 Environment Temperature 5 C 50 C Humudity 15 95 without condensation Device Standart EN 55011 2007 A2 2007 EN 61326 2006 EN 61000 3 2 2006 EN 61000 3 3 1995...

Страница 32: ...A CALCULATION CHART ACCORDING TO CAPACITOR CONNECTION FORMAT Capacitor Powers 3 Phase Connection Phase Neutral Connection Phase Neutral bridged Connection Phase Phase Connection Phase Phase bridged Co...