Energy

This is the section in which the actice, reactive (ind. and cap.) 

and apparent energies consumed one by one in each phase 

and, the total active, reactive (ind. and cap.) and apparent 

energy consumed in total of the system are monitored.

If required, “Reset” selection is pressed (eg.when the counter 

is read for invoicing purpose). Entering the password, “Delete 

counters ?” question appears on the screen. In case of 

pressing “Yes”, all the counters are deleted.

P.S.: Password process is described in this section.  

Counter Index

The index value of electrical counter 

connected to the plant is entered in 

this section. Thus, the energies 

recorded by electrical counter are 

compared.

P.S.: VARkombi-12-PC-TFT-OG 

does not use these values for 

compensation.

Press “Setings” selection first 

inorder to enter energy values.

Sub-screen will change and red 

frame will appear on the index line. 

Red frame is moved to the line of 

which value will be entered by using 

direction keys and, “Select” key is 

pressed.

An underline in blue colour appears 

in the line with red frame. The value 

of number in the digit  under which 

the  blue line is, is entered by using 

up and down keys. Then, move to 

the next digit by left key. When all 

the digits are changed with the same 

figures in the counter, “Apply” key is 

pressed. When the values of all 

lines are entered, “Okay” key is 

pressed and, when “Save Changes” 

appears on the screen, the data are 

kept in the memory by pressing 

“Okay” key.

Settings

This is the section in which you can find all set-up regarding 

the device. Password is entered. After commissioning of 

VARkombi-12-PC-TFT-OG, any change of parameters is not 
required normally. 

However, it may be necessary for the 

users requring to create  special conditions or make some 

adjustments. 

1 7

1 6

1 5

2 3

5 6

8 9

11 12

30

KWh

(Active)

7

4

1

10

Exit

Σ

-L1-L2-L3

Reset

KVARh

(ind.)

KVARh

(cap.)

KVAh

(apparent)

000003035 137

000000108 131

000000087 291

000003058 151

Total

Select

ESC

1 7

SET-UP

Target TanΦ - CosΦ

Switch On Time
Switch Off  Time
Min. Step Time

2 3

5 6

8 9

11 12

7

4

1

10

30

1

2 3

5 6

8 9

11 12

30

KWh

(Active)

7

4

1

10

14

Exit

Settings

KVARh

(ind.)

KVARh

(cap.)

000000056 321

000000001 031

000000000 291

2 3

5 6

8 9

11 12

30

KWh

(Active)

7

4

1

10

Cancel

Yes

KVARh

(ind.)

KVARh

(cap.)

KVAh

(apparent)

000003035 137

000000108 131

000000087 291

000003058 151

Delete

 Counters?

No

Counter Index

2 3

5 6

8 9

11 12

30

KWh

(Active)

7

4

1

10

KVARh

(ind.)

KVARh

(cap.)

000000056 321

000000001 031

000000000 291

Counter Index

2 3

5 6

8 9

11 12

30

KWh

(Active)

7

4

1

10

Exit

Select

KVARh

(ind.)

KVARh

(cap.)

000000056 321

000000001 031

000000000 291

Counter Index

Apply

▲ +

▼ -

2 3

5 6

8 9

11 12

30

KWh

(Active)

7

4

1

10

KVARh

(ind.)

KVARh

(cap.)

000000056 321

000000001 031

000000000 291

Counter Index

Cancel

Okay

Exit

2 3

5 6

8 9

11 12

30

KWh

(Active)

7

4

10

KVARh

(ind.)

KVARh

(cap.)

000000056 321

000000001 031

000000000 291

Counter Index

Cancel

Okay

Exit

Save

changes

1

1 7 9 7

Measurement Types

9

Содержание VARkombi-12-PC-TFT-OG

Страница 1: ...dislik Elektronik Tic ve San Ltd ti Reactive Power Control Relay Industrial Facilities Markets Oil Stations Schools Workshops Hotels 12 Step VARkombi 12 PC TFT OG Connection type selective VARkombi 12...

Страница 2: ...7 8 Current Transformer Primary Value 1 7 9 Number of Steps 1 7 10 Advanced Set up Menu 1 7 10 1 T on Transition Delay Time 1 7 10 2 T off Transition Delay Time 1 7 10 3 Current Flow Direction Detecti...

Страница 3: ...ver Temperature 1 7 10 6 2 4 Voltage THD Setting 1 7 10 6 2 5 Voltage HD Setting 1 7 10 6 2 6 Current THD Setting 1 7 10 6 2 7 Current HD Setting 1 7 10 6 3 Fan Settings 1 7 10 6 3 1 Fan Temperature V...

Страница 4: ...the device for different purposes other than compensation system 6 Fix the device tightly on the control panel with the apparatus given on the device without hanging around 7 Do not interfere to the...

Страница 5: ...king compensation for the generator according to the second Cos 2 set up Displaying many guiding screens operating system is used in the micro processor Computer communicated RS485 MODBUS RTU Password...

Страница 6: ...g to the specified current value The outputs of the steps are not needed to be made in any order However the first 6 steps can consist of triple phase capacitor groups It is recomended to connect sing...

Страница 7: ...er the other according to the priority Meanwhile the phase in which the alarm is given displayed on the screen Arrow keys can move between the alarms In case Select key is pressed during on any alarm...

Страница 8: ...e checked again in case any power of the steps and their connections are not intenalized for a long time 5 Step Learning of step powers For more info When all the steps are internalized the main scree...

Страница 9: ...umptions Instant consumption values of each phase and their scaled representation the normal under and over compensation of the phases their inductive capacitive characterized loads and whether the sy...

Страница 10: ...rol Otherwise the device remains in manual control continuously 1 2 3 4 5 6 7 8 9 11 10 12 30 Menu Cos PF Steps 0 R S T 0 ind cap ind cap ind cap S T Q 1 763K P 21 44K PF 0 991 0 155K 14 66K 0 999 1 4...

Страница 11: ...tep with red frame among the step boxes is displayed on the left side of the screen while moving with directon keys The information regarding the runtime of all steps number of switching phase or phas...

Страница 12: ...ave Changes appears on the screen the data are kept in the memory by pressing Okay key Settings This is the section in which you can find all set up regarding the device Password is entered After comm...

Страница 13: ...r DYN 5 NOTE The current transformer ratio must be entered in the section from the menu 1 7 8 select exit 1 7 Measurement types MV LV ratio Transformer Type 2 3 5 6 8 9 11 12 7 4 1 10 30 1 1 Enter MV...

Страница 14: ...1 10 30 Connection MEDIUM VOLTAGE LOW VOLTAGE Voltage become isolated The value of the voltage transformer must be entered NOTE The current transformer ratio must be entered in the section from the m...

Страница 15: ...or the deadline This causes delays in the compensation VARkombi 12 PC TFT OG It collects the energies ind cap active consumed Step activating and de activating periods are decreased or increased autom...

Страница 16: ...lows down by means of dynamic control of switch off time and continously do not make fast moves unnecessarily P S 1 Switch off time counts only for capacitor activated newly If necessary and a close s...

Страница 17: ...ge will appear on the screen When Okay key is pressed the value is taken into memory Enter cap penalty limit 2 3 5 6 8 9 11 12 7 4 1 10 30 Apply 10 Enter cap penalty limit 2 3 5 6 8 9 11 12 7 4 1 10 3...

Страница 18: ...s are entered in the same way by using the up and down keys Press Apply key inorder to take T off switching time into memory Save changes message will appear on the screen When Okay key is pressed the...

Страница 19: ...ation in some plants especially the plants in which the loads are changing very quickly The required status for function is selected by using the up and down keys Press Apply key inorder to take this...

Страница 20: ...2 3 5 6 8 9 11 12 7 4 1 10 14 30 Exit 3 phase Select R S T 1 Step 1 phase 0 000 KVAr 0 000 KVAr 0 000 KVAr 0 000 KVAr 2 3 5 6 8 9 11 12 7 4 1 10 30 3 phase R S T 1 Step 1 phase 0 000 KVAr 0 000 KVAr 0...

Страница 21: ...00 K Step Change 2 3 4 5 6 8 9 10 11 12 16 17 14 15 1 7 13 2 3 5 6 8 9 11 12 7 4 1 10 30 Exit Load New value Old value Old value R S T 0 000 K 0 000 K 0 000 K 0 000 K Step Change 2 3 4 5 6 8 9 10 11 1...

Страница 22: ...under compensation in any phase during the activation of alert device warns the user In this case Review the capacitor power distribution in the steps especially in the phase where the alert is given...

Страница 23: ...s may blowed out The fuses in the power line of capacitors may blowed out Removing the failure steps internalized zero should be internalized again 1 7 10 6 1 General Alarms Over Temperature enable 2...

Страница 24: ...digit All values are entered in the same way by using up and downkeys Select key is pressed to take them into the memory Save changes message will appear on the screen Pressing Okay key the value is...

Страница 25: ...essing Okay key the value is taken into the memory 5 005 Voltage HD Alarm Setting HDV Save Changes In case harmonic protection is activated in the step protection function Chapter 1710643 all steps ar...

Страница 26: ...0 30 Apply disable Fan Output 1 7 10 6 4 Setting Advanced Setting Menu Alarm Protection Step Protection Function De activation of the capacitors is recommended to protect them against temperature volt...

Страница 27: ...30 Apply Enable User Password Status 2 3 5 6 8 9 11 12 7 4 1 10 30 Exit Password active passive Password change 1 7 9 7 2 PASSWORD Enter old password 0 2 3 5 6 8 9 11 12 7 4 1 10 30 Exit Password acti...

Страница 28: ...ssword should be entered to write data This is the section in which the password is entered The value is setup to the required value by using the up and down key starting from the digit where the blue...

Страница 29: ...ing Okay key the value is taken into the memory Device No 001 255 The value is setup to the required value by using the up and down key starting from the digit where the blue line is Then left key is...

Страница 30: ...ting Values THD Current 30 Alarm Setting Values HD Current 30 Fan Settings Fan Temperature Value 50 C Fan Settings Fan Output disable Level Protection Function Temperature Protection disable Level Pro...

Страница 31: ...Class IP 20 Terminal Protection Class IP 00 Environment Temperature 5 C 50 C Humudity 15 95 without condensation Device Standart EN 55011 2007 A2 2007 EN 61326 2006 EN 61000 3 2 2006 EN 61000 3 3 1995...

Страница 32: ...A CALCULATION CHART ACCORDING TO CAPACITOR CONNECTION FORMAT Capacitor Powers 3 Phase Connection Phase Neutral Connection Phase Neutral bridged Connection Phase Phase Connection Phase Phase bridged Co...

Отзывы: